5. SOUND LEVELS
HEAT SOURCE
Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.
63
125
250
500
1k
2k
4k
8k
dB(A)
Standard
50/60Hz
45.5
59.5
59.5
51.5
48.0
45.5
47.5
43.0
56.5
Low noise mode
50/60Hz
66.0
54.0
54.0
47.5
47.0
48.5
43.0
39.5
54.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63
125
250
500
1k
2k
4k
8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum
audible limit on
continuous noise
Stand 50/60Hz
Low
50/60Hz
Sound level of PQHY-P600YLM-A