235
4. Installation
SYSTEM DESIGN
S.D. WR2
MEE15K036
4. Installation
4-1. Requirement on installation site
4-2. Spacing
In case of single installation, 600mm or more of back space as front space makes easier access when servicing the unit
from rear side.
1. No direct thermal radiation to the unit.
2. No possibility of annoying the neighbors by the sound of the unit.
Valves and refrigerant flow on the Heat source unit may generate noise.
3. Avoid the sites where strong winds blow.
4. With strength to bear the weight of the unit.
5. Drain flow from the unit is cared at heating mode.
6. Enough space for installation and service as shown at 4-2.
7. Avoid the sites where acidic solutions or chemical sprays (sulfur series) are used frequently.
8. The unit should be secure from combustible gas, oil, steam, chemical gas like acidic solution, sulfur gas and so on.
Unit: mm (in.)
control box
The space for
replacement
(front side)
Service space
(front side)
Service space
Top view
control box
The space for
replacement
600(23-5/8)
450(17-3/4)
600(23-5/8)
450(17-3/4)
350(13-13/16)
880(34-11/16)
0000003813.BOOK 235 ページ 2015年11月11日 水曜日 午後4時4分
Содержание PQHY-P200-900Y(S)LM-A
Страница 1: ...PQHY P200 900Y S LM A PQRY P200 900Y S LM A MODEL ...
Страница 245: ...SYSTEM DESIGN 242 MEE15K036 ...