233
3. Piping Design
SYSTEM DESIGN
S.D. WR2
MEE15K036
3-3. Refrigerant charging calculation
Sample connection (with 3 BC controller and 6 indoor units) (PQRY-P700YSLM)
<Amount of additional refrigerant to be charged>
Calculating the amount of additional refrigerant to be charged
BC controller (Main BC)
IU
a
IU
C
b
IU
1 : P50
2 : P250
Joint kit
IU
Joint
BC controller (Sub BC)
BC controller (Sub BC)
B
c
d
IU
f
D
E
Joint
A
IU
e
F
H
* Refer to the
installation manual for
the connection.
G
3 : P15
4 : P20
5 : P140
6 : P200
Amount of additional refrigerant to be charged
Refrigerant for extended pipes (field piping) is not factory-charged to the heat source unit. Add an appropriate amount of refrigerant for each pipes on site.
Record the size of each high pressure pipe and liquid pipe, and the amout of refrigerant that was charged on the heat source unit for future reference.
Calculating the amount of additional refrigerant to be charged
The amount of refrigerant to be charged is calculated with the size of the on-site-installed high pressure pipes and liquid pipes, and their length.
Calculate the amount of refrigerant to be charged according to the formula below.
Round up the calculation result to the nearest 0.1kg. (i.e., 16.03 kg = 16.1 kg)
Units "m" and "kg"
<Formula>
• When the piping length from the heat source unit to the farthest indoor unit is 30.5 m (100 ft) or shorter
Amount of
additional
charge (kg)
=
High-pressure pipe
ø28.58 total length
× 0.36 (kg/m)
+
High-pressure pipe
ø22.2 total length
× 0.23 (kg/m)
+
High-pressure pipe
ø19.05 total length
× 0.16 (kg/m)
+
High-pressure pipe
ø15.88 total length
× 0.11 (kg/m)
+
Liquid pipe ø15.88
total length
× 0.2 (kg/m)
+
Liquid pipe ø12.7
total length
× 0.12 (kg/m)
+
Liquid pipe ø9.52
total length
× 0.06 (kg/m)
+
Liquid pipe ø6.35
total length
× 0.024 (kg/m)
BC controller
Amount
(to be added for standard or
main BC controller)
+
+
Main BC controller
Amount
Standard/Main
3.0kg
HA-type
2.0kg
+
Number of sub BC
controllers
Amount
(to be added for sub
BC controller)
+
Total capacity of connected
indoor units
Amount
(to be added for
indoor unit)
1
1.0kg
80 or below
2.0kg
2
2.0kg
81 to 160
2.5kg
161 to 330
3.0kg
331 to 390
3.5kg
391 to 480
4.5kg
481 to 630
5.0kg
631 to 710
6.0kg
711 to 800
8.0kg
801 to 890
9.0kg
891 to 1070
10.0kg
1071 to 1250
12.0kg
1251 or above
14.0kg
+
Heat source unit model
Amount
(to be added for
heat source unit)
Single
P550
1.0kg
P600
1.0kg
Heat source Twinning kit (High/Low press.)
CMY-Q100CBK2, CMY-Q200CBK:
The Low press. kit must be placed in the heat source unit that has a larger capacity index
of the two, regardless of the relative positions of the heat source units or their addresses.
(If heat source units that have the same capacity are used in combination, the distributor
can be placed in either heat source unit.)
The High press. kit is to be installed in the field.
HU
(Sub unit)
HU
(Main unit)