3. Piping Design
SYSTEM DESIGN
234
S.D. WR2
MEE15K036
Amount of factory charged refrigerant
The above calculation result of the amount of refrigerant to be charged must become below the value in the table below.
heat source unit
Model
P300
P250
P350
P500
P450
P550
P400
P600
P200
Charged amount
6.0 kg
11.7 kg
5.0 kg
Limitation of the amount of refrigerant to be charged
Sample calculation
Indoor
A: ø28.58
40m
1: 50
a: ø6.35
B: ø9.52
10m
2: 250
b: ø9.52
C:
3: 15
c: ø6.35
ø12.70
20m
4: 20
d: ø6.35
D:
5: 140
e: ø9.52
ø9.52
5m
6: 200
The total length of each liquid line is as follows:
ø28.58: A = 40 m
ø22.20: F + G = 4 m
ø12.70: C = 20 m
ø9.52: B + D + E + b + e + f = 35 m
ø6.35: a + c + d = 25 m
Therefore,
<Calculation example>
Additional refrigerant charge
= 40 × 0.33 + 4 × 0.21 + 20 × 0.11 + 35 × 0.054 + 25 × 0.021 + 3
+ 2 + 2 + 6
= 31.7 (31.655) kg
f: ø9.52
E: ø9.52
5m
F: ø22.20
3m
10m
5m
5m
10m
5m
5m
G: ø22.20
1m
• When the piping length from the heat source unit to the farthest indoor unit is longer than 30.5 m (100 ft)
Amount of
additional
charge (kg)
=
High-pressure pipe
ø28.58 total length
× 0.33 (kg/m)
+
High-pressure pipe
ø22.2 total length
× 0.21 (kg/m)
+
High-pressure pipe
ø19.05 total length
× 0.14 (kg/m)
+
High-pressure pipe
ø15.88 total length
× 0.1 (kg/m)
+
Liquid pipe ø15.88
total length
× 0.18 (kg/m)
+
Liquid pipe ø12.7
total length
× 0.11 (kg/m)
+
Liquid pipe ø9.52
total length
× 0.054 (kg/m)
+
Liquid pipe ø6.35
total length
× 0.021 (kg/m)
+
Main BC controller
Amount
HA-type
2.0kg
+
Number of sub BC
controllers
Amount
(to be added for sub
BC controller)
+
Total capacity of connected
indoor units
Amount
(to be added for
indoor unit)
1
1.0kg
80 or below
2.0kg
2
2.0kg
81 to 160
2.5kg
161 to 330
3.0kg
331 to 390
3.5kg
391 to 480
4.5kg
481 to 630
5.0kg
631 to 710
6.0kg
711 to 800
8.0kg
801 to 890
9.0kg
891 to 1070
10.0kg
1071 to 1250
12.0kg
1251 or above
14.0kg
Total index of the heat source units
P200
P250
P300
P350
P400
P450
P500
P550
P400
P450
P500
P550
P600
YLM
YLM
YLM
YLM
YLM
YLM
YLM
YLM
YSLM
YSLM
YSLM
YSLM
YSLM
Maximum refrigerant charge
Factory charged
5.0kg
5.0kg
5.0kg
6.0kg
6.0kg
6.0kg
6.0kg 11.7kg
10.0kg 10.0kg 10.0kg 10.0kg 10.0kg
Charged on site
27.0kg 32.0kg 33.0kg 52.0kg 52.0kg 53.0kg 55.0kg 57.0kg
52.0kg 53.0kg 55.0kg 61.5kg 64.5kg
Total for system
32.0kg 37.0kg 38.0kg 58.0kg 58.0kg 59.0kg 61.0kg 68.7kg
62.0kg 63.0kg 65.0kg 71.5kg 74.5kg
P600
YLM
11.7kg
58.0kg
69.7kg
Total index of the heat source units
Maximum refrigerant charge
Factory charged
Charged on site
Total for system
P700
P800
P850
P900
YSLM
YSLM
YSLM
YSLM
12.0kg
12.0kg 12.0kg 12.0kg
72.0kg
74.0kg 76.0kg 76.0kg
84.0kg
P750
YSLM
12.0kg
74.0kg
86.0kg 86.0kg 88.0kg 88.0kg
+
BC controller
Amount
(to be added for standard or
main BC controller)
Standard/Main
3.0kg
+
Heat source unit model
Amount
(to be added for
heat source unit)
Single
P550
1.0kg
P600
1.0kg