IX
Troubleshooting ]
- 232 -
HWE09080
GB
1. Error
Code
Low pressure fault
2. Error definition and error detection method
When starting the compressor from Stop Mode for the first time if low pressure reads 0.098MPa [14psi] immediately before
start-up, the operation immediately stops.
3. Cause, check method and remedy
1301
Cause
Check method and remedy
(1)
Inner pressure drop due to a leakage.
Refer to the section on troubleshooting the low pressure
sensor.(page 307)
(2)
Low pressure sensor failure
(3)
Short-circuited pressure sensor cable due to
torn outer rubber
(4)
A pin on the male connector is missing.
(5)
Disconnected wire
(6)
Failure of the low pressure input circuit on the
controller board
Содержание PQHY-P120THMU-A
Страница 1: ......
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 83: ... 74 ...
Страница 102: ... III Heat source Unit Components 93 HWE09080 GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 103: ... 94 III Heat source Unit Components GB HWE09080 ...
Страница 105: ... 96 ...
Страница 113: ... 104 IV Remote Controller GB HWE09080 ...
Страница 115: ... 106 ...
Страница 130: ... 121 HWE09080 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 123 2 Principal Parts and Functions 126 ...
Страница 131: ... 122 ...
Страница 143: ... 134 VI Refrigerant Circuit GB HWE09080 ...
Страница 145: ... 136 ...
Страница 181: ... 172 VII Control GB HWE09080 ...
Страница 183: ... 174 ...
Страница 235: ... 226 ...
Страница 366: ... 357 HWE09080 GB X LED Monitor Display on the Heat source Unit Board 1 How to Read the LED on the Service Monitor 359 ...
Страница 367: ... 358 ...
Страница 414: ......