IX
Troubleshooting ]
- 271 -
HWE09080
GB
1. Error
Code
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. System
configuration
(2) Grouping of units in a system with multiple heat source units
6607
Error
source
address
Error display
Detection
method
Cause
Check method and remedy
LOSS-
NAY
(LC)
ME remote
controller (RC)
MA remote
controller (MA)
No acknowl-
edgement
(ACK) at IC
transmission to
LC
(1)
Factors (1) through (5) in the
"Factors in system with one
heat source unit" (When per-
forming an interlocked opera-
tion of the LOSSNAY unit
and the indoor units that are
connected to different heat
source units.)
1)
Turn off the power source of
heat source unit for 5 or more
minutes, and turn it on again. If
the error is accidental, it will
run normally.If not, check the
cause 2).
(2)
Disconnection or short circuit
of the transmission line for
the heat source unit on the
terminal block for centralized
control line connection (TB7)
2)
Check the causes of (1) - (5). If
the cause is found, correct it. If
no cause is found, check 3).
(3)
When multiple heat source
units are connected and the
power source of one of the
heat source units has been
shut off.
3)
Same cause as that for indoor
unit described in 3)
(4)
The male power supply con-
nector of the heat source unit
is not connected to the fe-
male power supply switch
connector (CN40).
(5)
The male power supply con-
nectors on 2 or more heat
source units are connected to
the female power supply
switch connector (CN40) for
centralized control.
If an error occurs, after the
unit runs normally once, the
following causes may be con-
sidered.
Total capacity error
(7100)
Capacity code error
(7101)
Error in the number of
connected units (7102)
Address setting error
(7105)
Содержание PQHY-P120THMU-A
Страница 1: ......
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 83: ... 74 ...
Страница 102: ... III Heat source Unit Components 93 HWE09080 GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 103: ... 94 III Heat source Unit Components GB HWE09080 ...
Страница 105: ... 96 ...
Страница 113: ... 104 IV Remote Controller GB HWE09080 ...
Страница 115: ... 106 ...
Страница 130: ... 121 HWE09080 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 123 2 Principal Parts and Functions 126 ...
Страница 131: ... 122 ...
Страница 143: ... 134 VI Refrigerant Circuit GB HWE09080 ...
Страница 145: ... 136 ...
Страница 181: ... 172 VII Control GB HWE09080 ...
Страница 183: ... 174 ...
Страница 235: ... 226 ...
Страница 366: ... 357 HWE09080 GB X LED Monitor Display on the Heat source Unit Board 1 How to Read the LED on the Service Monitor 359 ...
Страница 367: ... 358 ...
Страница 414: ......