1. Error
Code
Short-circuited IPM/Ground fault (Detail code 104)
2. Error definition and error detection method
When IPM/IGBT short damage or grounding on the load side is detected just before starting the inverter.
3. Cause, check method and remedy
Refer to section -6- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.
4250
Cause
Check method and remedy
(1)
Grounding fault compressor
Refer to IX [4] -6- (2) [2].
(2)
Inverter output related
Refer to IX [4] -6- (2) [1]-[4].