IX
Troubleshooting ]
- 276 -
HWE09080
GB
1. Error
Code
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. System
configuration
(3) System connected to the system controllers (MELANS)
6607
Error
source
address
Error display
Detection
method
Cause
Check method and remedy
System
controller
(SC)
ME remote
controller
(RC)
MA remote
controller
(MA)
No acknowl-
edgement
(ACK) at IC
transmission to
SC
1.
Error display on some displays on
ME remote controllers
Check (1) - (3) on the left.
(1)
Faulty wiring of the transmission
line for ME remote controller
(2)
Disconnection or contact failure of
the transmission connector for ME
remote controller
(3)
ME remote controller failure
2.
Error occurrence on all IC in the
system with one heat source unit
1)
Check the LED display for
troubleshooting on the heat
source unit.
(1)
An error is found by the heat source
unit.
Total capacity error (7100)
Capacity code error (7101)
Error in the number of connected
units (7102)
Address setting error (7105)
If an error is found, check
the check code definition,
and correct the error.
If no error is found, check
the cause 2)
(2)
Disconnection or short circuit of the
transmission line for the heat
source unit on the terminal block for
centralized control line connection
(TB7)
2)
Check (2) - (4) on the left.
(3)
Turn off the power source of the
heat source unit
(4)
Malfunction of electrical system for
the heat source unit
3.
Error display on all displays on ME
remote controllers
Check (1) - (4) on the left
(1)
Same causes as (1) - (4) described
in 2.
(2)
When the power supply unit for
transmission lines is used and the
male power supply connector is
connected to the female power sup-
ply switch connector (CN40) for the
transmission line for centralized
control
(3)
Disconnection or shutdown of the
power source of the power supply
unit for transmission line
(4)
System controller (MELANS) mal-
function
Содержание PQHY-P120THMU-A
Страница 1: ......
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 83: ... 74 ...
Страница 102: ... III Heat source Unit Components 93 HWE09080 GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 103: ... 94 III Heat source Unit Components GB HWE09080 ...
Страница 105: ... 96 ...
Страница 113: ... 104 IV Remote Controller GB HWE09080 ...
Страница 115: ... 106 ...
Страница 130: ... 121 HWE09080 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 123 2 Principal Parts and Functions 126 ...
Страница 131: ... 122 ...
Страница 143: ... 134 VI Refrigerant Circuit GB HWE09080 ...
Страница 145: ... 136 ...
Страница 181: ... 172 VII Control GB HWE09080 ...
Страница 183: ... 174 ...
Страница 235: ... 226 ...
Страница 366: ... 357 HWE09080 GB X LED Monitor Display on the Heat source Unit Board 1 How to Read the LED on the Service Monitor 359 ...
Страница 367: ... 358 ...
Страница 414: ......