131
CHAPTER 8 FUNCTIONS
8
8.
16
F
unct
ions
wit
h an
Ex
tens
ion
M
odul
e
Connec
ted
(c) Operation when an error occurs
Depending on whether the remote I/O signals of the extension I/O module are used as general-purpose I/O
signals or assigned for the external signal assignment function, the operation of the D/A converter module for
an error differs as shown in the following table.
*1
When the external signal assignment function is used, the operation of the D/A converter module is the same as that of
when the CLEAR is set for the digital output HOLD/CLEAR setting function, even if HOLD is set.
*2
When "HOLD" is set to Digital output HOLD/CLEAR setting, the Y signal of an extension digital output module is held at
the time of disconnection or CPU module STOP.
For different types of errors, the resulting error condition follows the following order of priority:
• Major error > Moderate error > Minor error > In disconnection, or the CPU module being in STOP status
Remote I/O signal
Remote input (RX)
Remote output (RY)
Digital output HOLD/CLEAR
setting function
CLEAR
HOLD
External signal assignment
function
Not assigned
Assigned
Not assigned
Assigned
Not assigned
Assigned
Status of the D/A
converter module
Minor error
Same as the normal operation
Same as the normal operation
Same as the normal operation
Moderate error
Clear
Same as the
normal operation
Clear
Same as the
normal operation
Clear
Same as the
normal operation
Major error
Clear
Clear
Clear
In disconnection,
or the CPU
module being in
STOP status
Clear
Same as the
normal operation
Clear
Same as the
normal operation
Hold
Same as the
normal operation