162
(4) When the MODE LED turns off
(5) When the D LINK LED turns off
(6) When the D LINK LED flashes
Check item
Action
Is the main D/A converter module in offset/gain setting mode?
When the main D/A converter module is in offset/gain setting, change the mode to
normal mode after the offset/gain setting is completed.
Does any hardware error occur?
If the MODE LED does not turn on even after the module power supply is turned on
from off, the hardware failure is a possible cause. Please consult your local Mitsubishi
representative.
Check item
Action
Does the own station in network operate normally?
Connect the engineering tool to the master station, and then check if a data link is
established in the own station by using CC-Link IE Field Network diagnostics.
(
User's manual for the master/local module used)
Are 1000BASE-T-compliant Ethernet cables used?
Replace the cable with a 1000BASE-T-compliant Ethernet cable.
(
User's manual for the master/local module used)
Is the station-to-station distance 100m or less?
Change the station-to-station distance to 100m or less.
Does the cabling condition (bend radius) meet the specifications?
Refer to the manual for the Ethernet cable used, and correct the bend radius.
Is any Ethernet cable disconnected?
Replace the Ethernet cable.
Do other stations connected to the main D/A converter module
operate normally?
Check if the power supplies of the other stations are turned on.
Does the switching hub normally operate?
• Check if a 1000BASE-T-compliant switching hub is used. (
User's manual for the
master/local module used)
• Check if the power supply of the switching hub is turned on.
Does the station number of the main D/A converter module overlap
with the other stations?
Two or more stations are overlapping.
Change the setting so that all the station numbers differ.
Check item
Action
Does the set station number of the main D/A converter module match
the station number of the main D/A converter module that is set up in
the network configuration settings of the master station or in the CC
IE Field configuration?
Match the station number of the main D/A converter module with the station number
that is set up in the network configuration settings of the master station or in the CC IE
Field configuration.
Is the station type remote device station?
Change the station type of the module to the remote device station in the network
configuration settings of the master station.
Is the A/D converter module a reserved station?
Change the setting of reserved/ignored error station to other than the reserved station
in the network configuration settings of the master station.
Is stop of the data link checked through CC-Link IE Field Network
diagnostics?
Check the link status through CC-Link IE Field Network diagnostics and start the link
when the data link is stopped.
Is the station number switch set to other than 1 to 120?
The setting range for the station number switch is 1 to 120. Set the number from 1 to
120.
Has the connection been changed to the other master station with a
different network number?
• Correct the connection to the previous master station.
• To communicate with the master station with a different network number, power off
and on the main D/A converter module.