206
(4) Current output characteristics
The following graph shows the current output characteristics.
*1
Set the offset value and gain value in the user range setting within the range satisfying the following two conditions:
• Setting range: 0 to 20mA
• ((Gain value) - (Offset value))
11.4mA
*2
The extension D/A converter modules does not support User range setting 2.
Use the value within the practical digital input range and practical analog output range. If a value is out of the range, the
maximum resolution and accuracy may not fall within the range of performance specifications. (Do not use the value in the
dotted line region in the above graph.)
No.
Output range setting
Offset value
Gain value
Digital value
Maximum resolution
1)
4 to 20mA
4mA
20mA
0 to 12000
1.66
A
2)
0 to 20mA
0mA
20mA
1.33
A
User range setting 2
(0 to 20mA)
0.95
A
1)
Digital input value
0
0
4
5
10
15
20
6000
12000
12287
-288
2)
Practical
analog
output range
Analog output
value (mA)
Содержание NZ2EX2B-60DA4