8.
9 Sc
al
ing F
unct
ion
(4) Example of the scaling setting
Ex.
1: When values are set for a channel with output range of 0 to 5V in the main D/A converter module as
follows:
• "CH
Scaling enable/disable setting": "0: Enable"
• "CH
Scaling upper limit value": 10000
• "CH
Scaling lower limit value": 2000
The digital values and scale-converted digital values are as follows:
Digital value
Digital value after scale conversion
Analog output voltage (V)
2000
0
0
3600
2400
1
5200
4800
2
6800
7200
3
8400
9600
4
10000
12000
5
0V
5V
Digital value after scale conversion
Analog output voltage (V)
Scaling lower limit
value: 2000
Scaling upper limit
value: 10000
0
12000 12287