CHAPTER 8 FUNCTIONS
8
8.
10 Shif
t F
u
nct
ion
●
If the digital value exceeds the range of -32768 to 32767 as a result of shift addition, the digital operation value is fixed to
the lower limit value (-32768) or the upper limit value (32767).
●
For the extension D/A converter module, go to "Ext. module 1_Module parameter" to set "Ext. module 1_CH
D/A
conversion enable/disable setting" to "0: Enable", and set a value to be added in CH
Shifting set value (RWw16 to
RWw19) of the extension D/A converter module.
(3) Setting example
Ex.
When values are set for a channel with output range of -10 to 10V in the main D/A converter module as
follows:
• CH
Shifting set value (RWw6 to RWw9): 250
The digital value is as follows:
Analog output voltage (V)
Digital value (before adjustment)
Digital value + Shifting set value (after adjustment)
-10
-16250
-16000
-5
-8250
-8000
0
-250
0
5
7750
8000
10
15750
16000
10
5
0
0
16000
15750
-16000
-16250
-5
Analog output voltage (V)
Adjusts with the shifting set value
Digital value
-10
Adds the shifting set value
1) Digital value
(before adjustment)
2) Digital value + Shifting set
value (after adjustment)
1) Digital value
(before
adjustment)
2) Digital value +
Shifting set value
(after adjustment)