(4) Remote READY
This signal is used as an interlock condition when the master station reads/writes data to/from the remote register
or remote buffer memory areas of the A/D converter module.
Upon turning on the module power supply, Remote READY (RXB) turns on.
As Error flag (RXA) turns on, Remote READY (RXB) turns off.
(a) Device number
The device number of this input signal is as follows:
(5) CH
A/D conversion completed flag
CH
A/D conversion completed flag (RX10 to RX13, RX20 to RX23) turns on as the A/D conversion is
completed in the A/D conversion enabled channels.
Turning on and off Initial data setting request flag (RY9) makes the signal return to the default state (off). When
A/D conversion is completed, the signal turns on.
(a) Device number
The device numbers of this input signal are as follows:
(6) CH
Difference conversion state flag
This signal allows the difference conversion status to be checked.
• Changing CH
Difference conversion trigger (RY14 to RY17, RY24 to RY27) from No request (OFF) to
Trigger request (ON) results in CH
Difference conversion state flag (RX14 to RX17, RX24 to RX27) turning
to Converting difference (ON).
• Changing CH
Difference conversion trigger (RY14 to RY17, RY24 to RY27) from Trigger request (ON) to
No request (OFF) results in CH
Difference conversion state flag (RX14 to RX17, RX24 to RX27) turning
from Converting difference (ON) to Not converted (OFF).
(a) Device number
The device numbers of this input signal are as follows:
Signal name
Main A/D converter module
Extension A/D converter module
Remote READY
RXB
Signal name
Main A/D converter module
Extension A/D converter module
CH1
CH2
CH3
CH4
CH1
CH2
CH3
CH4
CH
A/D conversion completed flag
RX10
RX11
RX12
RX13
RX20
RX21
RX22
RX23
Difference conversion status
CH
Difference conversion state flag (RX14 to RX17, RX24 to
RX27)
Not converted
OFF
Converting difference
ON
Signal name
Main A/D converter module
Extension A/D converter module
CH1
CH2
CH3
CH4
CH1
CH2
CH3
CH4
CH
Difference conversion state flag
RX14
RX15
RX16
RX17
RX24
RX25
RX26
RX27
Содержание NZ2EX2B-60AD4
Страница 1: ...CC Link IE Field Network Analog Digital Converter Module User s Manual NZ2GF2BN 60AD4 NZ2EX2B 60AD4 ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURES BEFORE OPERATION 4 Memo ...
Страница 156: ...154 3 In the dialog box that appears shown below click button ...
Страница 169: ...167 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo ...
Страница 253: ......