78
12.
Set "Method selection" to "Parameter write".
13.
Set "Write Value". Follow the next steps to set the value:
• Click the title cell of "Read Value" to select all the items and copy them.
• Click the title cell of "Write Value" to select all the items and paste the copy.
• Select the items to be changed, and set new values.
14.
Click
button to open the following window.
15.
Click
button.
16.
The parameters are written to the A/D converter module.
Setting up the module parameters of the slave station is now complete.
17.
Close the "CC IE Field Configuration" window.
[CC IE Field Configuration]
[Close with Reflecting the Setting]
18.
Click
button to open the refresh parameter setting window.