Appendix 2 Details of Re
mote Regist
ers
Appendix 2
Details of Remote Registers
This section describes the details of the remote registers for a master/local module.
The described assignment of device numbers assumes that the remote registers of the main module are assigned to
RWr0 to RWrF and RWw0 to RWwF.
(1) Latest error code
An error code is stored when a moderate error or major error occurs.
Turning on Error clear request flag (RYA) after eliminating the cause of the error clears the error code.
Errors that occurred in the past can be checked with Error history
(address: 0A00H to 0AEFH). For the error
history, refer to the following:
• Error history data
(
Page 222, Appendix 3 (23))
(a) Device number
The device number of this remote register is as follows:
(2) Latest warning code
An error code is stored when a minor error occurs. An alarm code is stored when an alarm occurs.
After a minor error has occurred, eliminating the cause of the error and then waiting for five seconds results in
Latest warning code (RWr1) being automatically cleared.
Errors or alarms that occurred in the past can be checked with Error history
(address: 0A00H to 0AEFH). For
error history, refer to the following:
• Error history data
(
(a) Device number
The device number of this remote register is as follows:
(3) CH
Digital operation value
The digital operation value which is obtained by the digital clipping function, scaling function, shift function, and
difference conversion function is stored as signed 16-bit binary.
(a) Device number
The device numbers of this remote register are as follows:
Remote register name
Main A/D converter module
Extension A/D converter module
Latest error code
RWr0
Remote register name
Main A/D converter module
Extension A/D converter module
Latest warning code
RWr1
Remote register name
Main A/D converter module
Extension A/D converter module
CH1
CH2
CH3
CH4
CH1
CH2
CH3
CH4
CH
Digital operation value
RWr2
RWr3
RWr4
RWr5
RWr12
RWr13
RWr14
RWr15
Содержание NZ2EX2B-60AD4
Страница 1: ...CC Link IE Field Network Analog Digital Converter Module User s Manual NZ2GF2BN 60AD4 NZ2EX2B 60AD4 ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURES BEFORE OPERATION 4 Memo ...
Страница 156: ...154 3 In the dialog box that appears shown below click button ...
Страница 169: ...167 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo ...
Страница 253: ......