118
(3) Example of the combined use of the digital clipping function and the scaling
function
Ex.
For the channel with the set input range of 0 to 5V, of the main A/D converter module, settings are made
as follows:
• "CH
Scaling enable/disable setting": "0: Enable"
• "CH
Scaling upper limit value": 24000
• "CH
Scaling lower limit value": 0
• "CH
Digital clipping enable/disable setting": "0: Enable"
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window
Select the main A/D converter module from "List of stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
In "Basic module parameter", set "CH
A/D conversion enable/disable setting" to "0: Enable".
Input voltage (V)
Digital output value
Digital operation value
-0.12
-384
0
0
0
0
1
3200
4800
2
6400
9600
3
9600
14400
4
12800
19200
5
16000
24000
5.12
16383
24000
1) Digital output value
Digital clipping
Output range: -384 to 16383
Output range: 0 to 16000
0
0
5
Analog input voltage (V)
Digital output value
1) Digital output value
3) Digital operation value
2) Value after digital clipping
3) Digital operation value
2) Value after digital clipping
Scaling
Upper limit value: 16000 24000
Lower limit value: 0 0
16000
16383
24000
-384
Содержание NZ2EX2B-60AD4
Страница 1: ...CC Link IE Field Network Analog Digital Converter Module User s Manual NZ2GF2BN 60AD4 NZ2EX2B 60AD4 ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURES BEFORE OPERATION 4 Memo ...
Страница 156: ...154 3 In the dialog box that appears shown below click button ...
Страница 169: ...167 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo ...
Страница 253: ......