231
APPX
A
Appendix 4 I/O Conversion
Character
istics of A/D Con
ver
sion
●
Use the value within the practical analog input range and practical digital output range. If a value is out of the range, the
maximum resolution and accuracy may not fall within the range of performance specifications. (Do not use the value in
the dotted line region in the graph of voltage input characteristics.)
●
Do not set the voltage over
±
15V. Doing so can cause breakdown of the elements.
(4) Current input characteristics
The following graph shows the current input characteristics.
*1
Set the offset value and gain value in the user range setting within the range satisfying the following conditions.
If the following conditions are not satisfied, A/D conversion may not be properly performed.
• Gain value
≤
20mA, offset value
≥
-20mA
• ((Gain value) - (Offset value))
≥
16mA
• 20.84mA
≥
(Gain value - (Offset value
×
2))
*2
When the analog input value exceeds the range of digital output values, the digital output value is fixed to the maximum
or minimum value.
*3
The extension A/D converter module does not support User range 2.
●
Use the value within the practical analog input range and practical digital output range. If a value is out of the range, the
maximum resolution and accuracy may not fall within the range of performance specifications. (Do not use the value in
the dotted line region in the graph of current input characteristics.)
●
Do not set the voltage over
±
30mA. Doing so can cause breakdown of the elements.
No.
Input range setting
Offset value
Gain value
Digital output value
Maximum resolution
1)
0 to 20mA
0mA
20mA
0 to 16000
1.25
μ
A
2)
4 to 20mA
4mA
20mA
1
μ
A
User range setting 2
(-20 to 20mA)
-16000 to 16000
1
μ
A
Input range setting
Digital output value
Minimum
Maximum
0 to 20mA
-384
16383
4 to 20mA
User range setting 2
(-20 to 20mA)
-16384
16383
16000
-16000
-16384
-20
-10
0
4
10
20
30
0
Practical analog input range
Analog input current (mA)
-30
-384
2)
1)
Digital output
value
Содержание NZ2EX2B-60AD4
Страница 1: ...CC Link IE Field Network Analog Digital Converter Module User s Manual NZ2GF2BN 60AD4 NZ2EX2B 60AD4 ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURES BEFORE OPERATION 4 Memo ...
Страница 156: ...154 3 In the dialog box that appears shown below click button ...
Страница 169: ...167 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo ...
Страница 253: ......