(4) Setting method (master station)
1.
Set the synchronization period of the master station to either of the following:
• 0.88ms
• 1.77ms
• 3.55ms
For details on the setting method, refer to the following:
When the master station is RJ71GF11-T2 or RJ71EN71:
MELSEC iQ-R Inter-Module Synchronization Function Reference Manual
When the master station is the simple motion module:
MELSEC-Q QD77GF Simple Motion Module User's Manual (Positioning Control)
Set the synchronization period of the master station, and "Conversion speed setting" and the number of conversion enabled
channels of the A/D converter modules so that the following conditions are satisfied:
Setting the number of conversion enabled channels beyond the limits shown above results in the error code (0E40H or
1E40H) being stored in Latest error code (RWr0), Error flag (RXA) turning on, and the ERR. LED turning on, with no A/D
conversion performed. In addition, the occurrence of an error (error code: 0E40H or 1E40H) during operation causes the A/D
conversion to be interrupted.
Set value in "Conversion
speed setting"
Synchronization period of the
master station
Number of conversion enabled channels (maximum)
Main A/D converter module
Extension A/D converter
module
0: 400
μ
s/channel; or 1:
1ms/channel
0.88ms
1
1
1.77ms
2
2
3.55ms
4
4
2: 100
μ
s/channel
• 0.88ms
• 1.77ms
• 3.55ms
4
4
Содержание NZ2EX2B-60AD4
Страница 1: ...CC Link IE Field Network Analog Digital Converter Module User s Manual NZ2GF2BN 60AD4 NZ2EX2B 60AD4 ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURES BEFORE OPERATION 4 Memo ...
Страница 156: ...154 3 In the dialog box that appears shown below click button ...
Страница 169: ...167 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo ...
Страница 253: ......