189
APPX
A
Appendix 1 Details of Re
mote I/O Signals
Appendix 1.1 Remote
input signals
APPENDICES
Appendix 1
Details of Remote I/O Signals
This section describes the details of remote I/O signals assigned to the master/local module.
The described assignment of device numbers assumes that the remote I/O signals of A/D converter modules are
assigned as follows:
Appendix 1.1
Remote input signals
(1) Warning flag
At the occurrence of a minor error, Warning flag (RX7) turns on.
Eliminating the cause of the minor error occurred and waiting for five seconds results in Latest warning code
(RWr1) turning to 0000H and Warning flag (RX7) turning off.
(a) Device number
The device number of this input signal is as follows:
Signal name
Main A/D converter module
Extension A/D converter module
Remote input signals
RX0 to RX1F
RX20 to RX2F
Remote output signals
RY0 to RY1F
RY20 to RY2F
Signal name
Main A/D converter module
Extension A/D converter module
Warning flag
RX7
Warning flag (RX7)
Latest warning code (RWr1)
Minor error
removed
OFF
ON
ON
OFF
0000H
Error code
Controlled by the A/D converter module
Minor error
occurred
Remote READY (RXB)
0000H
5 seconds elapsed
5 seconds
Содержание NZ2EX2B-60AD4
Страница 1: ...CC Link IE Field Network Analog Digital Converter Module User s Manual NZ2GF2BN 60AD4 NZ2EX2B 60AD4 ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURES BEFORE OPERATION 4 Memo ...
Страница 156: ...154 3 In the dialog box that appears shown below click button ...
Страница 169: ...167 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo ...
Страница 253: ......