Liquid pipe

Gas pipe

Felt tape (7) 

Indoor/outdoor unit 
connecting wire (A)

Piping tape (G)

2-5. PIPE FORMING AND DRAIN PIPING

2-5-1. PIPE FORMING

• Place the drain hose below the refrigerant piping.
• Make sure that the drain hose is not crowded or bent.
• Do not pull the hose when applying the tape.

‡ :KHQWKHGUDLQKRVHSDVVHVWKHURRPEHVXUHWRZUDSLWZLWKLQVXODWLRQPDWHULDO¿HOG

supplied).

Note:

Make sure not to damage the cover of refrigerant pipe when attaching it back on with 
screws.

Left or left-rear piping
Note:

Be sure to reattach the drain hose and the drain cap if the piping is being installed on left 
or bottom left of unit, otherwise, water could drip down from the drain hose.

3ODFHWKHUHIULJHUDQWSLSLQJDQGWKHGUDLQKRVHWRJHWKHUWKHQ¿UPO\DSSO\IHOWWDSH

from the end. 
Felt tape (7) overlap width should be 1/3 the tape width. Use a bandage stopper at the 
end of felt tape (7).

2) Pull out the drain cap at the back right of the indoor unit. (Fig. 1)

• Hold the convex section at the end and pull the drain cap.

3) Pull out the drain hose at the back left of the indoor unit. (Fig. 2)

• Hold the claw marked by the arrows and pull out the drain hose forward.

4) Put the drain cap into the section to which the drain hose is to be attached at the rear of 

the indoor unit. (Fig. 3)
• Insert a screwdriver into the hole on the cap and insert the cap fully into the drain 

pan.

5) Insert the drain hose fully into the drain pan at the back right of the indoor unit. (Fig. 4)

• Check if the hose is hooked securely to the projection of its inserting part at the 

drain pan.

6) Insert the drain hose into wall hole sleeve (C), and attach the upper part of indoor unit 

onto the installation plate (1). Then, shift the indoor unit completely to the left to make 
placing the piping in the back of the unit easier.

7) Cut out two pieces of cardboard from the shipping box (use any two pieces of the four 

pieces), roll each piece, hook them onto the back rib, and use them as spacer to lift the 
indoor unit. (Fig. 5)

8) Connect the refrigerant piping with the extension pipe (B).
9) Attach the lower part of the indoor unit into the installation plate (1).

Drain cap

Drain hose

Drain cap

Drain hose

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

2-4. INSTALLING THE L-JOINT

1) Install L-joint (10) on the back of the unit. Position L-joint (10) according to the piping 

direction. (Fig. 1)
In case of bottom piping (Fig. 2)
• Cut L-joint (10) at the position shown in Fig. 3.
• Remove union nut from the unit and install it to L-joint (10).
• Flare end of L-joint (10).

2) Use two torque wrenches to tighten the nut. (tighten torque 65 N•m) (Fig. 4)
3) Install charge nut (9) to the liquid refrigerant piping, which connects the indoor and out-

door unit.

4) Perform leak test of joint part (the part tightened in “2)”), the nut on the gas side should 

remain installed. 

5) Slide pipe cover of L-joint (10) and cover the joint. (Fig. 5)

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Remove panel for 
piping on bottom 
right side of unit

Remove panel 
for piping on right 
side of unit

Cut

Tightening
direction

Remove panel for piping on 
left side of unit.

Piping tape (G)

Felt tape (7)

Slide the pipe cover 
completely to the end.

Содержание MSZ-D30NA

Страница 1: ... is dust blockage or loose parts on the power supply plug or the outlet it could FDXVH HOHFWULF VKRFN RU UH I ORRVH SDUWV DUH IRXQG RQ WKH SRZHU VXSSO SOXJ UHSODFH LW N Securely attach the electrical cover to the indoor unit and the service panel to the outdoor unit If the electrical cover of the indoor unit and or the service panel of the outdoor unit are QRW DWWDFKHG VHFXUHO GXVW ZDWHU HWF FRXOG...

Страница 2: ...oom On a rigid wall to reduce the possibility of vibration Where it is not exposed to direct sunlight Where it can be easily drained At a distance 3 ft 1 m or more away from a TV and radio Operation of the air conditioner may interfere with radio or TV reception An amplifier may be re quired for the affected device In a place as far away as possible from fluorescent and incandescent lights so the ...

Страница 3: ...Please leave the space as shown in the picture for maintenance usage After the leak test apply insulating mate rial tightly so that there is no gap Indoor unit Wall hole sleeve C Cut off the extra length Pipe attach ment strap E Use the wall hole sleeve C to prevent indoor out door connecting wire A from contacting metal parts in the wall and to protect the wiring from rodents Wall hole cover D Se...

Страница 4: ...appear less than 1 3 16 in 30 mm outside Fig 2 9 Process the end of ground wire Fig 3 Connect it to the ground terminal of electrical parts box 10 Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting ...

Страница 5: ...nit Fig 4 Check if the hose is hooked securely to the projection of its inserting part at the drain pan 6 Insert the drain hose into wall hole sleeve C and attach the upper part of indoor unit onto the installation plate 1 Then shift the indoor unit completely to the left to make placing the piping in the back of the unit easier 7 Cut out two pieces of cardboard from the shipping box use any two p...

Страница 6: ...pplied drain hose I Fig 2 When connecting the drain hose to a hard vinyl chloride pipe be sure to insert it securely into the pipe Fig 3 Do not make drain piping as shown below Do not raise Accumulated drain water Air Waving Water leakage Water leakage Water leakage Tip of drain hose dipped in water Ditch At least 1 31 32 in 50 mm gap Downward slope Drain hose Soft hose I D 19 32 in 15 mm Drain ho...

Страница 7: ...140 to 180 ø 3 8 9 52 3 8 22 34 3 to 41 2 25 to 30 350 to 420 ø 1 2 12 7 1 2 26 0 08 to 0 10 2 0 to 2 5 49 0 to 56 4 36 to 42 500 to 575 ø 5 8 15 88 5 8 29 73 5 to 78 4 54 to 58 750 to 800 4 1 PURGING PROCEDURES AND LEAK TEST 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe 2 Connect gauge manifold valve and vacuum pump to service port of stop valve on the gas pipe ...

Страница 8: ...ort of the stop valve on the gas pipe side of the outdoor unit 2 Fully close the stop valve on the liquid pipe side of the outdoor unit 3 Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 MPa Gauge 0 lbf in 2 0 kgf cm2 4 Start the emergency COOL operation To start the emergency operation in COOL mod...

Отзывы: