background image

1-3. SPECIFICATIONS

1-3-1. POWER SUPPLY AND INDOOR/OUTDOOR WIRE CONNECTION

• Power should be taken from an exclusive branched circuit.
• Wiring work should be based on applicable technical standards.
• Wiring connections should be made following the diagram.
• Securely tighten screws.

Connecting wires and the ground wire

• Use solid conductor AWG14 or stranded conductor AWG14.
• Use double insulated copper wire with 600 V insulation.
• Use copper conductors only.
* Follow local electrical codes.

Power supply cable and ground wire

• Use solid or stranded conductor AWG10.
• Use copper conductors only.
* Follow local electrical codes.

Note:

When the indoor unit is powered from the outdoor unit, depending on local code, a 
disconnect switch needs to be installed to a power supply circuit.

Pipe length

Up to 25 ft. (7.5 m)

No additional charge is re-

quired.

Exceeding 25 ft. (7.5 m)

Additional charge is required.

(Refer to the table below.)

• Refrigerant adjustment... If pipe length exceeds 25 ft. (7.5 m), additional refrigerant 

(R410A) charge is required.

(The outdoor unit is charged with refrigerant for pipe length up to 25 ft. [7.5 m])

Limits

Pipe length

100 ft. (30 m) max.

Height difference

 50 ft. (15 m) max.

No. of bends

10 max.

‡ 7KHXQLWKDVÀDUHGFRQQHFWLRQVRQERWKLQGRRUDQGRXWGRRUVLGHV

• Remove the valve cover from the outdoor unit, then connect the pipe.
• Refrigerant pipes are used to connect the indoor and outdoor units.
• Be careful not to crush or over bend the pipe in pipe bending.

1-3-2. REFRIGERANT PIPES

• To prevent condensation, insulate the two refrigerant pipes.
• Refrigerant pipe bending radius must be 4 in. (100 mm) or more.

 CAUTION

%HVXUHWRXVHWKHLQVXODWLRQRIVSHFL¿HGWKLFNQHVVWDEOHRQWKHULJKW([FHVVLYHLQVXOD

-

tion may cause incorrect installation of the indoor unit, and too little insulation may cause 
condensate to form.

Pipe

Outside

diameter

Minimum

wall thick-

ness

Insulation

thickness

Insulation material

inch (mm)

For liquid

3/8 (9.52)

0.0315 (0.8)

5/16 (8)

Heat resistant foam 

SODVWLF6SHFL¿F

gravity

For gas

5/8 (15.88)

0.0394 (1.0)

5/16 (8)

(OHFWULFDOVSHFL¿FDWLRQV

MODEL

MSY-D30NA MSY-D36NA MSZ-D30NA MSZ-D36NA

INDOOR UNIT

Power supply 
(V, PHASE, Hz)

208/230, 1, 60

Min. Circuit Ampacity (A)

1.0

Fan motor (F.L.A.)

(A)

0.76

OUTDOOR UNIT

Power supply 
(V, PHASE, Hz)

208/230, 1, 60

Max. Fuse size 
(time delay) 

(A)

25

Min. Circuit Ampacity (A)

21

Fan motor (F.L.A.)

(A)

0.93

Compressor

(R.L.A) (A)

16

(L.R.A) (A)

20

Control voltage

Indoor unit - Remote controller: (Wireless)

Indoor unit - Outdoor unit: DC12-24 V (Polar)

1-2. SELECTING THE INSTALLATION LOCATION

Refrigerant to be added

MSZ-D30/36NA

2.96 oz. each 5 ft. (55 g/m)

MSY-D30/36NA

1.08 oz. each 5 ft. (20 g/m)

INDOOR UNIT 

‡ :KHUHDLUÀRZLVQRWEORFNHG

• Where cool air aspreads over the entire room.
• On a rigid wall to reduce the possibility of vibration.
• Where it is not exposed to direct sunlight.
• Where it can be easily drained.
• At a distance 3 ft. (1 m) or more away from a TV and 

radio. Operation of the air conditioner may interfere 
with radio or TV reception. An amplifier may be re-
quired for the affected device.

• In a place as far away as possible from fluorescent 

and incandescent lights (so the infrared remote control 
can operate the air conditioner normally).

:KHUHWKHDLU¿OWHUFDQEHUHPRYHGDQGUHSODFHGHDVLO\

Note:

Install the indoor unit high on the wall where air can dis-
tribute over the entire room.

REMOTE CONTROLLER 

• Where it is convenient to operate and easily visible.
• Where children cannot easily touch it.

‡ 6HOHFWDSRVLWLRQDERXWIWPDERYHWKHÀRRU

Check that signals from the remote controller from 
that position are received by the indoor unit (‘beep’ 
or ‘beep beep’ receiving tone sounds). Then, attach 
remote controller holder to a pillar or wall and install 
wireless remote controller.

Note:

,QURRPVZKHUHLQYHUWHUW\SHÀXRUHVFHQWODPSVDUHXVHG

the signal from the wireless remote controller may not be 
received.

OUTDOOR UNIT

• Where it is not overly exposed to strong winds.

‡ :KHUHDLUÀRZLVJRRGDQGGXVWOHVV

• Where neighbours are not annoyed by operation 

sound or hot air.

• Where rigid wall or support is available to prevent the 

increase of operation sound or vibration.

• Where there is no risk of combustible gas leakage.
• If installing the unit in a location high above the ground, 

be sure to secure the unit legs.

• Where it is at least 10 ft. (3 m) away from the antenna 

of TV set or radio. Operation of the air conditioner may 
interfere with radio or TV reception in areas where re-

FHSWLRQ LV ZHDN $Q DPSOL¿HU PD\ EH UHTXLUHG IRU WKH

affected device.

• Install the unit horizontally.
• Please install it in an area not affected by snowfall or 

blowing snow. In areas with heavy snow, please install 

DFDQRS\DSHGHVWDODQGRUEDIÀHERDUGV

Note:

• It is advisable to make a piping loop near outdoor unit 

so as to reduce vibration.

‡ )RU LQFUHDVHG HI¿FLHQF\ LQVWDOO WKH RXWGRRU XQLW LQ D

location where continuous direct sunlight or excessive 
water can be avoided as much as possible.

Note:

When operating the air conditioner in low outside tem-
perature, be sure to follow the instructions described 
below.
• Never install the outdoor unit in a place where its air 

inlet/outlet side may be exposed directly to wind.

• To prevent exposure to wind, install the outdoor 

unit with its air inlet side facing the wall and 

DEDIÀH

board on the air outlet side.

Avoid the following places for installation where air 
conditioner trouble is liable to occur.

‡ :KHUHÀDPPDEOHJDVFRXOGOHDN

• Where there is an excessive amount of machine oil 

in the air.

• Salty places such as the seaside.
• Where sulfide gas is generated such as a hot 

spring.

• Where there is high-frequency or wireless equipment.

Содержание MSZ-D30NA

Страница 1: ... is dust blockage or loose parts on the power supply plug or the outlet it could FDXVH HOHFWULF VKRFN RU UH I ORRVH SDUWV DUH IRXQG RQ WKH SRZHU VXSSO SOXJ UHSODFH LW N Securely attach the electrical cover to the indoor unit and the service panel to the outdoor unit If the electrical cover of the indoor unit and or the service panel of the outdoor unit are QRW DWWDFKHG VHFXUHO GXVW ZDWHU HWF FRXOG...

Страница 2: ...oom On a rigid wall to reduce the possibility of vibration Where it is not exposed to direct sunlight Where it can be easily drained At a distance 3 ft 1 m or more away from a TV and radio Operation of the air conditioner may interfere with radio or TV reception An amplifier may be re quired for the affected device In a place as far away as possible from fluorescent and incandescent lights so the ...

Страница 3: ...Please leave the space as shown in the picture for maintenance usage After the leak test apply insulating mate rial tightly so that there is no gap Indoor unit Wall hole sleeve C Cut off the extra length Pipe attach ment strap E Use the wall hole sleeve C to prevent indoor out door connecting wire A from contacting metal parts in the wall and to protect the wiring from rodents Wall hole cover D Se...

Страница 4: ...appear less than 1 3 16 in 30 mm outside Fig 2 9 Process the end of ground wire Fig 3 Connect it to the ground terminal of electrical parts box 10 Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting ...

Страница 5: ...nit Fig 4 Check if the hose is hooked securely to the projection of its inserting part at the drain pan 6 Insert the drain hose into wall hole sleeve C and attach the upper part of indoor unit onto the installation plate 1 Then shift the indoor unit completely to the left to make placing the piping in the back of the unit easier 7 Cut out two pieces of cardboard from the shipping box use any two p...

Страница 6: ...pplied drain hose I Fig 2 When connecting the drain hose to a hard vinyl chloride pipe be sure to insert it securely into the pipe Fig 3 Do not make drain piping as shown below Do not raise Accumulated drain water Air Waving Water leakage Water leakage Water leakage Tip of drain hose dipped in water Ditch At least 1 31 32 in 50 mm gap Downward slope Drain hose Soft hose I D 19 32 in 15 mm Drain ho...

Страница 7: ...140 to 180 ø 3 8 9 52 3 8 22 34 3 to 41 2 25 to 30 350 to 420 ø 1 2 12 7 1 2 26 0 08 to 0 10 2 0 to 2 5 49 0 to 56 4 36 to 42 500 to 575 ø 5 8 15 88 5 8 29 73 5 to 78 4 54 to 58 750 to 800 4 1 PURGING PROCEDURES AND LEAK TEST 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe 2 Connect gauge manifold valve and vacuum pump to service port of stop valve on the gas pipe ...

Страница 8: ...ort of the stop valve on the gas pipe side of the outdoor unit 2 Fully close the stop valve on the liquid pipe side of the outdoor unit 3 Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 MPa Gauge 0 lbf in 2 0 kgf cm2 4 Start the emergency COOL operation To start the emergency operation in COOL mod...

Отзывы: