4-4. EXPLANATION TO THE USER

• Using the OPERATING INSTRUCTIONS, explain to the user how to use the 

DLUFRQGLWLRQHUWKHUHPRWHFRQWUROOHUUHPRYLQJWKHDLU¿OWHUVSODFLQJRUUHPRY

-

ing the remote controller from the remote controller holder, cleaning methods, 
precautions for operation, etc.)

• Recommend that the user read the OPERATING INSTRUCTIONS carefully.

Caution:

• After test run or remote signal reception check, turn off the unit with the 

E.O. SW or the remote controller before turning off the power supply. If this 
procedure is not performed, the unit will automatically begin operation when 
power supply is resumed.

To the user

• After installing the unit, explain to the user about auto restart function. 
• If auto restart function is unnecessary, it can be deactivated. Consult the 

service representative to deactivate the function. Refer to the service man-
ual for details.

4-2. TEST RUN

1) Insert power supply plug into the power outlet and/or 

turn on the breaker. 

2) Press the E.O. SW once. Test run will be performed 

for 30 minutes. If the left operation indicator light blinks 
every 0.5 seconds, inspect the indoor/outdoor unit con-
necting wire (A). After the test run, emergency COOL 
mode (75ºF [24ºC] COOL) will start.

3) To stop operation, press the E.O. SW several times 

until all LED lamps turn off. Refer to operating instruc-
tions for details. 

Checking the remote (infrared) signal reception
Press the ON/OFF button on the remote controller and listen for an audible indicator 
from the indoor unit. Press the ON/OFF button again to turn the air conditioner off.
• Once the compressor stops, the restart preventive device operates so the compres-

sor will not operate for 3 minutes to protect the air conditioner.

4-3. AUTO RESTART FUNCTION

This product is equipped with an auto restart function. When the power supply is cut off 
during operation, such as during blackouts, the function automatically starts opera-
tion in the previous setting once the power supply is resumed. (Refer to the operating 
instructions for details.) 

5-3. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following 
the procedure below so that refrigerant is not released into the atmosphere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas 

pipe side of the outdoor unit.

2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so 

that it can be easily closed fully when the pressure gauge shows 0 MPa [Gauge] (0 
lbf/in.

2

 [0 kgf/cm

2

]).

4) Start the emergency COOL operation.

To start the emergency operation in COOL mode, disconnect the power supply plug 
and/or turn off the breaker. After 15 seconds, connect the power supply plug and/or 
turn on the breaker, and then press the E.O. SW once. (The emergency COOL op-
eration can be performed continuously for up to 30 minutes.)

5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure 

gauge shows 0.05 to 0 MPa [Gauge] (approx. 7.25 to 0 lbf/in

2

 [0.5 to 0 kgf/cm

2

]).

6) Stop the emergency COOL operation.

To stop operation, press the E.O. SW several times until all LED lamps turn off. Re-
fer to operating instructions for details.

5. RELOCATING THE UNIT / MAINTENANCE

5-1. REMOVING AND INSTALLING THE PANEL ASSEMBLY

Removal procedure (Fig. 1, 2)

1) Remove the three screws that attach the panel assembly.
2) Open the front panel.
3) Remove the two screws that attach the panel assembly.

5HPRYHWKHSDQHODVVHPEO\%HVXUHWRUHPRYHLWVERWWRPHQG¿UVW

5-2. REMOVING THE INDOOR UNIT

Remove the bottom of the indoor unit from the installation plate. (Fig. 1, 2)

• Remove the panel assembly. (Refer to 5-1)

‡ ,QVHUWÀDWVFUHZGULYHUVLQWRWKHVTXDUHKROHVDWWKHOHIWDQGULJKWERWWRPRIWKHLQGRRU

unit and push them up; the bottom of the indoor unit goes down and the hooks are 
released.
*1 Remove the screw.
*2 Remove the tab of corner box from the indoor unit, and pull the corner box.
*3 Pull the indoor unit to remove.

Installation procedure (Fig. 3, 4)

1) Point the horizontal vane slightly downward. 
2) Attach the bottom of the panel assembly under the horizontal vane.
3) Fit in the top of the panel assembly.
4) Fit in the bottom of the panel assembly and tighten it using screws.
5) Push the section of the front panel marked by the arrows to close the front panel se-

curely.

Emergency operation switch
(E.O. SW)

Fig. 3

Horizontal vane

Fig. 4

Square hole

Push Lower

Corner box

Fig. 1

Fig. 2

Fig. 1

Fig. 2

When pumping down the refrigerant, stop the compressor before disconnecting 
the refrigerant pipes. The compressor may burst if air etc. get into it.

 WARNING

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, 
TOKYO 100-8310, JAPAN

Содержание MSZ-D30NA

Страница 1: ... is dust blockage or loose parts on the power supply plug or the outlet it could FDXVH HOHFWULF VKRFN RU UH I ORRVH SDUWV DUH IRXQG RQ WKH SRZHU VXSSO SOXJ UHSODFH LW N Securely attach the electrical cover to the indoor unit and the service panel to the outdoor unit If the electrical cover of the indoor unit and or the service panel of the outdoor unit are QRW DWWDFKHG VHFXUHO GXVW ZDWHU HWF FRXOG...

Страница 2: ...oom On a rigid wall to reduce the possibility of vibration Where it is not exposed to direct sunlight Where it can be easily drained At a distance 3 ft 1 m or more away from a TV and radio Operation of the air conditioner may interfere with radio or TV reception An amplifier may be re quired for the affected device In a place as far away as possible from fluorescent and incandescent lights so the ...

Страница 3: ...Please leave the space as shown in the picture for maintenance usage After the leak test apply insulating mate rial tightly so that there is no gap Indoor unit Wall hole sleeve C Cut off the extra length Pipe attach ment strap E Use the wall hole sleeve C to prevent indoor out door connecting wire A from contacting metal parts in the wall and to protect the wiring from rodents Wall hole cover D Se...

Страница 4: ...appear less than 1 3 16 in 30 mm outside Fig 2 9 Process the end of ground wire Fig 3 Connect it to the ground terminal of electrical parts box 10 Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting ...

Страница 5: ...nit Fig 4 Check if the hose is hooked securely to the projection of its inserting part at the drain pan 6 Insert the drain hose into wall hole sleeve C and attach the upper part of indoor unit onto the installation plate 1 Then shift the indoor unit completely to the left to make placing the piping in the back of the unit easier 7 Cut out two pieces of cardboard from the shipping box use any two p...

Страница 6: ...pplied drain hose I Fig 2 When connecting the drain hose to a hard vinyl chloride pipe be sure to insert it securely into the pipe Fig 3 Do not make drain piping as shown below Do not raise Accumulated drain water Air Waving Water leakage Water leakage Water leakage Tip of drain hose dipped in water Ditch At least 1 31 32 in 50 mm gap Downward slope Drain hose Soft hose I D 19 32 in 15 mm Drain ho...

Страница 7: ...140 to 180 ø 3 8 9 52 3 8 22 34 3 to 41 2 25 to 30 350 to 420 ø 1 2 12 7 1 2 26 0 08 to 0 10 2 0 to 2 5 49 0 to 56 4 36 to 42 500 to 575 ø 5 8 15 88 5 8 29 73 5 to 78 4 54 to 58 750 to 800 4 1 PURGING PROCEDURES AND LEAK TEST 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe 2 Connect gauge manifold valve and vacuum pump to service port of stop valve on the gas pipe ...

Страница 8: ...ort of the stop valve on the gas pipe side of the outdoor unit 2 Fully close the stop valve on the liquid pipe side of the outdoor unit 3 Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 MPa Gauge 0 lbf in 2 0 kgf cm2 4 Start the emergency COOL operation To start the emergency operation in COOL mod...