background image

Installation plate (1)

Center of 
ø 3 in. 
(75 mm) 
hole

8-11/16 in. 

(220 mm) 

or more 

4-11/16 in. 
(120 mm) 
or more 

2-13/16 in. (70 mm) or more

5-1/8 in. (130 mm) or more for left 
and left back piping (using spacer)

Ceiling

Wall

Wall

Attachment screw (2)

* Same for left hole.

Insert

the
scale. *

Align the 

scale with 
the line. *

Level

• Make ground wire a little longer than 

others. (More than 1-9/16 in. [40 mm])

2-1. ATTACHING THE INSTALLATION PLATE 

• Find a stud in the wall to attach installation plate (1) horizontally on the wall with screws (2).
• To prevent installation plate (1) from vibrating, be sure to install the attachment screws 

in the holes indicated in the illustration. For added support, additional screws may also 
be installed in other holes.

‡ ,IWKHUHFHVVHGEROWLVWRRORQJFKDQJHLWIRUDVKRUWHURQH¿HOGVXSSOLHG

2. INDOOR UNIT INSTALLATION

Wall

Outdoor side

2-2. DRILLING

1) Determine where the holes will be located on the wall.
2) Drill a ø 3 in. (75 mm) hole. The outdoor side should be 6/32 to 9/32 in. (5 to 7 mm) 

lower than the indoor side.

3) Insert wall hole sleeve (C).

2-3. CONNECTING WIRES FOR INDOOR UNIT

Note:

When the indoor unit is powered from the outdoor unit, depending on local code, a discon-
nect switch needs to be installed to a power supply circuit.

1) Open the front panel.
2) Place the upper part of the indoor unit on the installation plate.
3) Remove electrical cover.
4) Remove VA clamp.
5) Remove corner box.
6) Remove cable guide.
7) Remove conduit plate.
8) Attach conduit pipe (for rear piping) / elbow joint (for right, left, or downward piping) to 

conduit plate with lock nut. The thread of the installed conduit pipe / elbow joint appear-
ing inside should be less than 3/8 in. (10 mm). (Fig. 1) Elbow joint should appear less 
than 1-3/16 in. (30 mm) outside. (Fig. 2)

9) Process the end of ground wire (Fig. 3). Connect it to the ground terminal of electrical 

parts box.

10) Process the end of indoor/outdoor unit connecting wire (A) (Fig.3). Attach it to the 

terminal block. Be careful not to make mis-wiring. Attach the wire to the terminal block 
securely so that its core cannot be seen, and no external force affects the connecting 
section of the terminal block. 

11) Firmly tighten the terminal screws. After tightening, verify that the wires are tightly fas-

tened.

12) Reinstall conduit plate.
13) Reinstall cable guide.
14) According to the piping direction, remove the shaded part of the left side of box (Fig.4) 

or corner box (Fig. 5).

15) Reinstall VA clamp.
16) Reinstall electrical cover.
17) Reinstall panel assembly.

6/32-9/32 in.
(5-7 mm)

ø 3 in.
(75 mm)

Lead
wire

5/8 in.
(15 mm)

2-3/16 in.
(55 mm)

Less than 3/8 in.
(10 mm)

Conduit plate

Conduit pipe or 
elbow joint

Lock nut

Elbow joint   

(for right, left, or downward piping)

Less than 1-3/16 in. 
(30 mm)

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Corner box

Remove panel 
for piping on right 
side of unit

Remove panel for 
piping on bottom 
side of unit

Fig. 5

Box

Remove panel for piping 
on bottom left side of unit

Remove panel 
for piping on 
left side of unit

4 in. 

(100 mm)  

Remark:
* A disconnect switch should be 

required.
Check the local code.

** Use a ring tongue terminal in 

order to connect a ground wire 
to terminal.

Power supply 
208/230 V AC, 
1phase 2 wires, 
60 Hz

INDOOR UNIT

Terminal block

208/230 V AC 
1phase, 60 Hz

OUTDOOR UNIT

Terminal

block 1

Ground

Grounding terminal**

Grounding
terminal**

Disconnect
switch*

Pull tab to remove cable guide.

• Connect wires to the appropri-

ate terminals

• For future servicing, leave some 

slack in the connecting wires.

Electrical cover

VA Clamp

Indoor
terminal
block

Electrical box

Cable guide

Grounding
terminal

Conduit pipe

Lock nut

Conduit plate

Elbow joint

Conduit plate

or

Содержание MSZ-D30NA

Страница 1: ... is dust blockage or loose parts on the power supply plug or the outlet it could FDXVH HOHFWULF VKRFN RU UH I ORRVH SDUWV DUH IRXQG RQ WKH SRZHU VXSSO SOXJ UHSODFH LW N Securely attach the electrical cover to the indoor unit and the service panel to the outdoor unit If the electrical cover of the indoor unit and or the service panel of the outdoor unit are QRW DWWDFKHG VHFXUHO GXVW ZDWHU HWF FRXOG...

Страница 2: ...oom On a rigid wall to reduce the possibility of vibration Where it is not exposed to direct sunlight Where it can be easily drained At a distance 3 ft 1 m or more away from a TV and radio Operation of the air conditioner may interfere with radio or TV reception An amplifier may be re quired for the affected device In a place as far away as possible from fluorescent and incandescent lights so the ...

Страница 3: ...Please leave the space as shown in the picture for maintenance usage After the leak test apply insulating mate rial tightly so that there is no gap Indoor unit Wall hole sleeve C Cut off the extra length Pipe attach ment strap E Use the wall hole sleeve C to prevent indoor out door connecting wire A from contacting metal parts in the wall and to protect the wiring from rodents Wall hole cover D Se...

Страница 4: ...appear less than 1 3 16 in 30 mm outside Fig 2 9 Process the end of ground wire Fig 3 Connect it to the ground terminal of electrical parts box 10 Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting ...

Страница 5: ...nit Fig 4 Check if the hose is hooked securely to the projection of its inserting part at the drain pan 6 Insert the drain hose into wall hole sleeve C and attach the upper part of indoor unit onto the installation plate 1 Then shift the indoor unit completely to the left to make placing the piping in the back of the unit easier 7 Cut out two pieces of cardboard from the shipping box use any two p...

Страница 6: ...pplied drain hose I Fig 2 When connecting the drain hose to a hard vinyl chloride pipe be sure to insert it securely into the pipe Fig 3 Do not make drain piping as shown below Do not raise Accumulated drain water Air Waving Water leakage Water leakage Water leakage Tip of drain hose dipped in water Ditch At least 1 31 32 in 50 mm gap Downward slope Drain hose Soft hose I D 19 32 in 15 mm Drain ho...

Страница 7: ...140 to 180 ø 3 8 9 52 3 8 22 34 3 to 41 2 25 to 30 350 to 420 ø 1 2 12 7 1 2 26 0 08 to 0 10 2 0 to 2 5 49 0 to 56 4 36 to 42 500 to 575 ø 5 8 15 88 5 8 29 73 5 to 78 4 54 to 58 750 to 800 4 1 PURGING PROCEDURES AND LEAK TEST 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe 2 Connect gauge manifold valve and vacuum pump to service port of stop valve on the gas pipe ...

Страница 8: ...ort of the stop valve on the gas pipe side of the outdoor unit 2 Fully close the stop valve on the liquid pipe side of the outdoor unit 3 Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 MPa Gauge 0 lbf in 2 0 kgf cm2 4 Start the emergency COOL operation To start the emergency operation in COOL mod...

Отзывы: