3-1. CONNECTING WIRES FOR OUTDOOR UNIT

1) Remove the service panel.
2) Remove the conduit cover.
3) Attach the conduit connector to conduit cover with lock nut then secure it against unit 

with screws.

4) Connect ground wires of indoor/outdoor unit connecting wire (A) and power supply cord 

(K)  to the TB support.

5) Loosen the terminal screw, and attach indoor/outdoor unit connecting wire (A) from the 

indoor unit correctly on the terminal block. Attach the wire to the terminal block securely 
so that its core cannot be seen, and no external force affects the connecting section of 
the terminal block. 

6) Firmly tighten the terminal screws. After tightening, verify that the wires are tightly fas-

tened.

7) Connect power supply cord (K).
8) Install the conduit cover.
9) Install the service panel securely.

Terminal block

to conduit cover

Power supply cord (K)

3. OUTDOOR UNIT INSTALLATION

Power supply cord (K)

Indoor/outdoor unit 
connecting wire (A)

• Make ground wire a little longer than oth-

ers. (More than 1-3/8 in. [35 mm])

• For future servicing, leave some slack in 

the connecting wires.

Lead
wire

5/8 in.
(15 mm)

1-3/8 in.
(35 mm)

Service panel

Lock nut

Conduit cover

Connector

Grounding
terminal

2-5-2. DRAIN PIPING

• If the extension drain hose has to pass through a room, be sure to wrap it with in-

VXODWLRQ¿HOGVXSSOLHG

• The drain hose should point downward for easy drain. (Fig. 1)

‡ ,IWKHGUDLQKRVHSURYLGHGZLWKWKHLQGRRUXQLWLVWRRVKRUWFRQQHFWLWZLWKD¿HOG

supplied drain hose (I). (Fig. 2)

• When connecting the drain hose to a hard vinyl chloride pipe, be sure to insert it 

securely into the pipe. (Fig. 3)

Do not make drain piping as shown below.

Do not raise

Accumulated
drain water

Air

Waving

Water
leakage

Water
leakage

Water
leakage

Tip of drain 
hose dipped 
in water

Ditch

At least
1-31/32 in. 
(50 mm) 
gap

Downward
slope

Drain
hose

Soft hose I.D. 
19/32 in. 
(15 mm)

Drain hose

Hard vinyl chloride pipe 
I.D. 1-3/16 in.
(30 mm)

Insert
securely

Different
diameter joint

27-9/16 in.
(70 cm)
 or more

Fig. 1

Fig. 2

Fig. 3

Rear or bottom piping

3ODFHWKHUHIULJHUDQWSLSLQJDQGWKHGUDLQKRVHWRJHWKHUWKHQ¿UPO\DSSO\SLSLQJWDSH*

from the end.

2) Insert the piping and the drain hose into the wall hole sleeve (C), and attach the upper 

part of the indoor unit on the installation plate (1).

3) Check if the indoor unit is attached securely on the installation plate (1) by moving the 

unit to left and right.

4) Attach the lower part of the indoor unit into the installation plate (1).

Right piping
Note:

Before performing the following, make sure that wiring is completed, and the conduit cover 
is installed. (Refer to 2-3.)
1) Place the refrigerant piping and the drain hose together, shift them to left side of the 

XQLWDQGWKHQ¿UPO\DSSO\SLSLQJWDSH*IURPWKHHQG

2) Insert the piping and the drain hose into the wall hole sleeve (C), and attach the upper 

part of the indoor unit on the installation plate (1).

3) Check if the indoor unit is attached securely on the installation plate (1) by moving the 

unit to left and right.

4) Attach the lower part of the indoor unit into the installation plate (1).

Cut off in case of down-
ward piping.

TB support

Содержание MSZ-D30NA

Страница 1: ... is dust blockage or loose parts on the power supply plug or the outlet it could FDXVH HOHFWULF VKRFN RU UH I ORRVH SDUWV DUH IRXQG RQ WKH SRZHU VXSSO SOXJ UHSODFH LW N Securely attach the electrical cover to the indoor unit and the service panel to the outdoor unit If the electrical cover of the indoor unit and or the service panel of the outdoor unit are QRW DWWDFKHG VHFXUHO GXVW ZDWHU HWF FRXOG...

Страница 2: ...oom On a rigid wall to reduce the possibility of vibration Where it is not exposed to direct sunlight Where it can be easily drained At a distance 3 ft 1 m or more away from a TV and radio Operation of the air conditioner may interfere with radio or TV reception An amplifier may be re quired for the affected device In a place as far away as possible from fluorescent and incandescent lights so the ...

Страница 3: ...Please leave the space as shown in the picture for maintenance usage After the leak test apply insulating mate rial tightly so that there is no gap Indoor unit Wall hole sleeve C Cut off the extra length Pipe attach ment strap E Use the wall hole sleeve C to prevent indoor out door connecting wire A from contacting metal parts in the wall and to protect the wiring from rodents Wall hole cover D Se...

Страница 4: ...appear less than 1 3 16 in 30 mm outside Fig 2 9 Process the end of ground wire Fig 3 Connect it to the ground terminal of electrical parts box 10 Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting ...

Страница 5: ...nit Fig 4 Check if the hose is hooked securely to the projection of its inserting part at the drain pan 6 Insert the drain hose into wall hole sleeve C and attach the upper part of indoor unit onto the installation plate 1 Then shift the indoor unit completely to the left to make placing the piping in the back of the unit easier 7 Cut out two pieces of cardboard from the shipping box use any two p...

Страница 6: ...pplied drain hose I Fig 2 When connecting the drain hose to a hard vinyl chloride pipe be sure to insert it securely into the pipe Fig 3 Do not make drain piping as shown below Do not raise Accumulated drain water Air Waving Water leakage Water leakage Water leakage Tip of drain hose dipped in water Ditch At least 1 31 32 in 50 mm gap Downward slope Drain hose Soft hose I D 19 32 in 15 mm Drain ho...

Страница 7: ...140 to 180 ø 3 8 9 52 3 8 22 34 3 to 41 2 25 to 30 350 to 420 ø 1 2 12 7 1 2 26 0 08 to 0 10 2 0 to 2 5 49 0 to 56 4 36 to 42 500 to 575 ø 5 8 15 88 5 8 29 73 5 to 78 4 54 to 58 750 to 800 4 1 PURGING PROCEDURES AND LEAK TEST 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe 2 Connect gauge manifold valve and vacuum pump to service port of stop valve on the gas pipe ...

Страница 8: ...ort of the stop valve on the gas pipe side of the outdoor unit 2 Fully close the stop valve on the liquid pipe side of the outdoor unit 3 Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 MPa Gauge 0 lbf in 2 0 kgf cm2 4 Start the emergency COOL operation To start the emergency operation in COOL mod...