F1
F2
F3
F4
Night setback
Setting display:
Night setback Yes
Temp. range 19 - 28
Start 23:00
Stop 5:00
6. Night setback
Button operation
Main
[2]
The current settings will appear.
Press the
SELECT
button to go to the setting screen.
[1]
Select "Night setback" from the Timer menu, and press the
SELECT
but-
ton.
This control starts heating operation when the control object group is stopped and the room temperature drops below the pre-
set lower limit temperature. Also, this control starts cooling operation when the control object group is stopped and the room
temperature rises above the preset upper limit temperature.
The Night setback function is not available if the operation and the temperature setting are performed from the remote control-
ler.
If the room temperature is measured by the air-conditioner's suction temperature sensor, the accurate temperature may not
be obtained when the air-conditioner is inactive or when the air is not clean. In this case, switch the sensor to a remote sensor
(PAC-SE40TSA/PAC-SE41TS-E) or a remote control sensor.
[3]
Move the cursor to the desired item with the
F1
or
F2
button out of Night
setback No (disable)/Yes (enable), Temp. range, Start time, or Stop time.
Change the settings with the
F3
or
F4
button.
• Temp. range:
The lower limit temperature (for heating operation) and the
upper limit temperature (for cooling operation) can be set. The
temperature difference between the lower and upper limits
must be 4°C (8°F) or more. The settable temperature range
varies depending on the connected indoor units.
* 1°C increments
• Start/Stop time:
settable in 5-minute increments
*Press and hold the button to rapidly advance the numbers.
Press the
SELECT
button to save the settings.
A confirmation screen will appear.
P
Navigating through the screens
• To go back to the Main menu .................. MENU button
• To return to the previous screen ............... RETURN button
Night setback
Night setback
Select:
Cursor
Main menu:
Night setback No /
Yes
Temp. range 19 - 28
Start 23:00
Stop 5:00
Night setback
Yes
Temp. range 19 - 28
Start 23:00
Stop 5:00
Changes saved
Cur.
Night setback
Night setback
Select:
Cursor
Main menu:
Night setback No /
Yes
Temp. range 19 - 28
Start 23:00
Stop 5:00
Night setback
Yes
Temp. range 19 - 28
Start 23:00
Stop 5:00
Changes saved
Cur.
Main menu:
Cursor
Timer menu
Timer
Weekly timer
OU silent mode
Night setback
F1
F2
F3
F4
F1
F2
F3
F4
F1
F2
F3
F4
MA REMOTE CONTROLLER
6
. FUNCTION SETTINGS [P
AR-40MAA]
D-27