57
(6) Specify the error codes targeted for notification.
You can use this setting to specify which of the errors
that occur in air conditioning units will be reported.
You can choose from the following 3 options:
[All]
Reports all error codes.
[A.C. unit only (no delay)]
Error delay codes are not reported.
[Set error codes]
Only the specified error codes are reported.
If you selected "
Set error codes
", enter the target error
codes.
You can specify up to 10 error codes.
You can also specify wildcards. However, if you specify a wildcard in an error code, all the subsequent
digits are also taken as wildcards.
Note that you cannot enter a wildcard at the beginning of the code.
E.g.) 2*
-- All error codes from 2000 to 2999
2*50 -- Illegal specification.
**01 -- Illegal specification.
(7) Specify the error codes that will be masked from error
notification.
You can use this to specify error codes that will not be
reported (that will be masked) when errors occur in
an air conditioning unit.
You can specify up to 10 error codes.
You can also specify wildcards. However, if you specify
a wildcard in an error code, all the subsequent digits
are also taken as wildcards.
Note that you cannot enter a wildcard at the beginning of the code.
E.g.) 2* -- All error codes from 2000 to 2999
2*50 -- Illegal specification.
**01 -- Illegal specification.
NOTE:
If the error codes targeted for notification and the masked error codes include the same error codes,
the message shown below appears.
If there is an overlap, the masking specification has priority.
If necessary, specify the settings again correctly.