20
1.4.3.3 In case for remote connection (E-mail)
In the case when on line monitoring is applied to local air conditioning system (with G-50A installed) from the
Maintenance Tool in the remote place via mail server.
All communication to G-50A is converted in E-mail in this case.
(1) After clicking "G-50A(Network)" on the selection screen of
Monitor mode, and click "REMOTE CONNECTION(E-mail)."
Last click " ."
(2) The mail connection setting screen is displayed.
Here, set the mail information on G-50A to be connected,
and that on the Maintenance Tool.
(a)Setting of the mail information on G-50A
1) To assign the G-50A connected in the past
After assigning “Customer name” from the pull down menu, select G-50A name.”
2) To connect to new G-50A
Click to open the address book, and register and select the mail address of G-50A.
*The 10 Customer names in the past are displayed on the pull down menu. To assign earlier G-50A,
open the address book to select.
NOTE:
•
To use the E-mail connection mode, the version of G-50A should be above 2.60.
•
When using E-mail connection mode, the local G-50A is required to be initially set with Maintenance Tool and
the mail address by the G-50A initial setting tool.
- For each mail address, it is required to obtain and set an exclusive one. To transmit mail via an internet
provider, obtain the mail address from the provider. When a mail server is existing on the LAN, obtain the
mail address from the LAN administrator.
- Set the [Pop receive interval] within 3 minutes. However to monitor operating status [Operation Monitor], set it within 1
minute.
- Setting of initial information to G-50A can not be executed from Maintenance Tool. Make sure to set it from the G-50A
initial setting tool locally. If dialup connection environment is available, it can be set from a remote position.
(For detail, please refer to 6-1 Mail Basic Setting in the instruction manual of the G-50A initial setting tool.)
•
The communication speed under E-mail connection mode largely depends on the transfer rate of each mail
server. Under the circumstance, the action of Maintenance Tool may take a lot of time under some internet
environments or routing mail servers.
•
For the system composition, please refer to the system diagram of (2)-2 in 1.1.2.
NOTE:
For each mail address, it is required to obtain and set an exclusive
one. To transmit mail via an internet provider, obtain the mail
address from the provider. When a mail server is existing on the
LAN, obtain the mail address from the LAN administrator.