4 ERROR CODE LIST
4.2 C Controller Module Dedicated Functions
181
4
-292
FEDCH
■
Program memory shutdown error
The shutdown processing of the program memory failed.
• Check if files in the program memory are being accessed.
• Check if all files in the program memory have been closed.
-293
FEDBH
■
Data memory shutdown error
The shutdown processing of the data memory failed.
• Check if files in the data memory are being accessed.
• Check if all files in the data memory have been closed.
-295
FED9H
■
Selected operation is being checked
The CCPU_SetDotMatrixLED function was executed while
checking the selected operation.
Execute the CCPU_SetDotMatrixLED function after checking the
operation.
-296
FED8H
■
Setting data size error
The setting data size is out of range.
Check the setting data size.
-297
FED7H
■
Input/output number, network number incorrect
specification
An input/output number out of the range (other than 000H to
FFFH or 3E0H to 3E3H) was specified.
Correct the argument of the function.
-298
FED6H
■
Input/output number, network number incorrect
specification
An input/output number with no module was specified.
-299
FED5H
■
Input/output number, network number incorrect
specification
• An input/output number of a module which does not
support the function was specified.
• The dedicated instruction was specified with the specified
module or mode.
Check the applicability of the dedicated function (such as the
support status and executable mode) by referring to the manual for
relevant modules.
-300
FED4H
■
Input/output number, network number incorrect
specification
An input/output number of a module, that cannot be
specified, was specified.
Correct the argument of the function.
-301
FED3H
■
Input/output number, network number incorrect
specification
A network number out of the range (other than 1 to 239)
was specified.
-302
FED2H
■
Input/output number, network number incorrect
specification
A network number which does not exist was specified.
-303
FED1H
■
Input/output number, network number incorrect
specification
An I/O module or intelligent function module controlled by
other CPU modules was specified.
• Correct the argument of the function.
• Delete a module controlled by other CPU modules, which has
been specified by the link direct device, from the program.
• Specify the network module controlled by the host CPU module
with a link direct device.
-304
FED0H
■
Input/output number, network number incorrect
specification
The target module cannot be identified with a function to
specify an I/O module or intelligent function module.
(The character strings to specify the target module are
incorrect.)
Correct the argument of the function.
-305
FECFH
■
Input/output number, network number incorrect
specification
The specified I/O module or intelligent function module is in
the state where it cannot execute the function.
The possible cause is a hardware failure of the I/O module or
intelligent function module specified. Please consult your local
Mitsubishi representative.
-306
FECEH
■
Device, buffer memory incorrect specification
The specified device exceeded the usable range.
Correct the argument of the function.
-307
FECDH
■
Device, buffer memory incorrect specification
A device that cannot be specified was specified.
-308
FECCH
■
Program fault
The specified argument structure is incorrect.
-309
FECBH
■
Program fault
The specified number of devices is incorrect.
-310
FECAH
■
Operation error
An unusable character string for a function is specified.
-311
FEC9H
■
Operation error
Data out of the specifiable range was entered.
Error code
Description
Corrective action
Decimal
Hexadec
imal