4 ERROR CODE LIST
4.2 C Controller Module Dedicated Functions
179
4
-234
FF16H
■
Event wait error
An error other than timeout occurred while the function waits
for the event.
• Check if a program is forcibly being terminated.
• Check if the C Controller module is running normally.
• Reset the C Controller module, or turn the power OFF and ON.
-235
FF15H
■
Number of event settings specification error
The specified number of event settings is out of range.
Check the number of specified event settings.
-236
FF14H
■
Remote operation specification code error
The remote operation specification code is out of range.
Check the specified remote operation specification code.
-237
FF13H
■
Detailed information character string specification error
The length of the specified character string was out of range
or characters which cannot be specified was specified.
Correct the length of the specified character string or character
string data.
■
Application code specification error
Five or more digits of the hexadecimal number was
specified for the application code.
Change the specified application code.
-238
FF12H
■
Event log registration error
Registering an event log failed.
Reset the C Controller module, or turn the power OFF and ON.
-239
FF11H
■
Drive insertion error
Either of the following functions executed with no drive
inserted.
• CCPU_UnmountMemoryCard
• CCPU_mountMemoryCard
Check if a drive is inserted.
-240
FF10H
■
Clock data incorrect error
The clock data to be set or the read clock data is incorrect.
• Check the clock data to be set.
• If this error occurs when reading the clock data, set the data
again.
-241
FF0FH
■
Cycle specification error
• The specified cycle is out of range.
• The cycle was set even when it had already been set.
• Check the specified cycle.
• Check if the cycle has been already set.
-242
FF0EH
■
Synchronization type specification error
The specified synchronization type is out of range.
Check the specified synchronization type.
-245
FF0BH
■
Not executable during interrupt service routine
A function was executed from interrupt service routine
without specifying '1' (ISR) to the call source flag.
Specify '1' to the call source flag (ISR) and execute the function
again.
-246
FF0AH
■
Timer event registration error
Registering a timer event failed.
• Retry.
• Check if the C Controller module is running normally.
• Reset the C Controller module, or turn the power OFF and ON.
-247
FF09H
■
Program number specification error
The specified program number is out of range or
unavailable.
• SFC program number (0 to 255)
• Servo program number (0 to 4095)
Correct the specified program number.
-248
FF08H
■
Number of starting axes specification error
9 or more starting axes were specified.
Correct the specified number of starting axes.
-249
FF07H
■
Axis type specification error
An axis type other than the axis/encoder axis/cam axis was
specified.
Correct the specified axis type.
-250
FF06H
■
Axis number specification error
The specified axis number is out of the available range.
Correct the specified axis number.
-252
FF04H
■
Torque limit value specification error
The specified torque limit value is out of the available range.
Correct the specified torque limit value.
-253
FF03H
■
Device number specification error
• The specified device number is out of range.
• The specified bit device number is not a multiple of 16.
Correct the start device number of the specified device.
-254
FF02H
■
Device type specification error
The specified device type is unavailable.
Check the specified device type.
-255
FF01H
■
Size specification error
• The specified number of words is out of range.
• The specified size is 0.
Correct the specified start device number and number of words.
-256
FF00H
■
Response completion wait timeout error
A timeout occurred while waiting for completion of a
response of a processing requested to other CPU modules.
• Increase the timeout time specified to the argument.
• Review and correct the user program (including other tasks which
execute motion CPU interaction functions).
• Review the program used for the request destination CPU module
and correct it to perform the processing requested from other CPU
modules, for example, by adding the WAIT instruction.
Error code
Description
Corrective action
Decimal
Hexadec
imal
Содержание MELSEC iQ-R C
Страница 1: ...MELSEC iQ R C Controller Module Programming Manual ...
Страница 2: ......
Страница 201: ...I 199 MEMO ...
Страница 203: ...I 201 MEMO ...
Страница 207: ......