62
3 DETAILS OF FUNCTION
3.1 C Controller Module Dedicated Functions
CCPU_EndCCIEFBDataAssurance
This function ends data assurance for one link scan of CC-Link IE Field Network Basic.
■
Format
short CCPU_EndCCIEFBDataAssurance (unsigned short usGroupNo)
■
Argument
■
Description
• This function ends data assurance for one link scan of CC-Link IE Field Network Basic for the specified group.
• When the CCPU_EndCCIEFBDataAssurance function is executed, the cyclic transmission of the CC-Link IE Field Network
Basic function is restarted.
■
Return value
■
Relevant function
•
Page 103 CCPU_StartCCIEFBDataAssurance
Argument
Name
Description
IN/OUT
usGroupNo
Group No.
Specify a group number to end data assurance. (1 to 4)
IN
Return value
Description
0 (0000H)
Normal
Other than 0
Error
For details on the error, refer to the following chapter.