15 EXTERNAL DEVICE COMMUNICATION INSTRUCTION
15.4 Predefined Protocol Support Function Instruction
837
15
■
Control data
Device
Item
Description
Setting range
(s)+0
Completion status
The completion status is stored upon completion of the instruction.
When two or more protocols are executed, the execution result of the protocol
executed last is stored.
• 0: Normal completion
• Other than 0: Error completion (error code)
System
(s)+1
Resulting number of
executed protocols
The number of protocols executed by the SP.ECPRTCL instruction is stored.
Any protocol where an error occurred is also included in the execution number. If
the setting of setting data or control data contains an error, "0" is stored.
0, 1 to 8
(s)+2
Execution protocol
number 1
Specify the number of the protocol to be executed first.
1 to 64
User
(s)+3
Execution protocol
number 2
Specify the number of the protocol to be executed second.
0, 1 to 64
(s)+4
Execution protocol
number 3
Specify the number of the protocol to be executed third.
0, 1 to 64
(s)+5
Execution protocol
number 4
Specify the number of the protocol to be executed fourth.
0, 1 to 64
(s)+6
Execution protocol
number 5
Specify the number of the protocol to be executed fifth.
0, 1 to 64
(s)+7
Execution protocol
number 6
Specify the number of the protocol to be executed sixth.
0, 1 to 64
(s)+8
Execution protocol
number 7
Specify the number of the protocol to be executed seventh.
0, 1 to 64
(s)+9
Execution protocol
number 8
Specify the number of the protocol to be executed eighth.
0, 1 to 64
(s)+10
Collation match
Receive packet
number 1
If receiving is included in the communication type of the protocol that has been
executed first, the receive packet number successful in collation match is stored.
If the communication type is "receive only", "0" is stored. If an error occurs
during execution of the first protocol, "0" is stored.
0, 1 to 16
System
(s)+11
Collation match
Receive packet
number 2
If receiving is included in the communication type of the protocol that has been
executed second, the receive packet number successful in collation match is
stored. If the communication type is "receive only", "0" is stored. If an error
occurs during execution of the second protocol, "0" is stored. If the number of
protocols executed is less than 2, "0" is stored.
0, 1 to 16
(s)+12
Collation match
Receive packet
number 3
If receiving is included in the communication type of the protocol that has been
executed third, the receive packet number successful in collation match is
stored. If the communication type is "receive only", "0" is stored. If an error
occurs during execution of the third protocol, "0" is stored. If the number of
protocols executed is less than 3, "0" is stored.
0, 1 to 16
(s)+13
Collation match
Receive packet
number 4
If receiving is included in the communication type of the protocol that has been
executed fourth, the receive packet number successful in collation match is
stored. If the communication type is "receive only", "0" is stored. If an error
occurs during execution of the fourth protocol, "0" is stored. If the number of
protocols executed is less than 4, "0" is stored.
0, 1 to 16
(s)+14
Collation match
Receive packet
number 5
If receiving is included in the communication type of the protocol that has been
executed fifth, the receive packet number successful in collation match is stored.
If the communication type is "receive only", "0" is stored. If an error occurs
during execution of the fifth protocol, "0" is stored. If the number of protocols
executed is less than 5, "0" is stored.
0, 1 to 16
(s)+15
Collation match
Receive packet
number 6
If receiving is included in the communication type of the protocol that has been
executed sixth, the receive packet number successful in collation match is
stored. If the communication type is "receive only", "0" is stored. If an error
occurs during execution of the sixth protocol, "0" is stored. If the number of
protocols executed is less than 6, "0" is stored.
0, 1 to 16
(s)+16
Collation match
Receive packet
number 7
If receiving is included in the communication type of the protocol that has been
executed seventh, the receive packet number successful in collation match is
stored. If the communication type is "receive only", "0" is stored. If an error
occurs during execution of the seventh protocol, "0" is stored. If the number of
protocols executed is less than 7, "0" is stored.
0, 1 to 16
(s)+17
Collation match
Receive packet
number 8
If receiving is included in the communication type of the protocol that has been
executed eighth, the receive packet number successful in collation match is
stored. If the communication type is "receive only", "0" is stored. If an error
occurs during execution of the eighth protocol, "0" is stored. If the number of
protocols executed is less than 8, "0" is stored.
0, 1 to 16
Содержание MELSEC iQ-F FX5
Страница 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Страница 2: ......
Страница 17: ...15 CONTENTS ...
Страница 24: ...22 MEMO ...
Страница 25: ...23 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW 2 PRECAUTIONS ON PROGRAMMING ...
Страница 126: ...124 6 SEQUENCE INSTRUCTIONS 6 3 Output Instructions Operation error There is no operation error ...
Страница 132: ...130 6 SEQUENCE INSTRUCTIONS 6 3 Output Instructions Operation error There is no operation error ...
Страница 140: ...138 6 SEQUENCE INSTRUCTIONS 6 3 Output Instructions Operation error There is no operation error ...
Страница 191: ...7 BASIC INSTRUCTIONS 7 2 Arithmetic Operation Instructions 189 7 Operation error There is no operation error ...
Страница 202: ...200 7 BASIC INSTRUCTIONS 7 2 Arithmetic Operation Instructions Operation error There is no operation error ...
Страница 278: ...276 7 BASIC INSTRUCTIONS 7 4 Bit Processing Instructions Operation error There is no operation error ...
Страница 280: ...278 7 BASIC INSTRUCTIONS 7 4 Bit Processing Instructions Operation error There is no operation error ...
Страница 915: ...18 TYPE CONVERSION FUNCTIONS 18 13 Converting DWORD to WORD 913 18 Operation error There is no operation error ...
Страница 917: ...18 TYPE CONVERSION FUNCTIONS 18 14 Converting DWORD to INT 915 18 Operation error There is no operation error ...
Страница 932: ...930 18 TYPE CONVERSION FUNCTIONS 18 26 Converting DINT to WORD Operation error There is no operation error ...
Страница 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Страница 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Страница 1107: ...I 1105 MEMO ...
Страница 1111: ......