8 APPLICATION INSTRUCTION
8.19 Initial State
• The switch functions shown in the table below are assigned to each of the devices specified for selector switches in the
operation mode. When X20 is assigned, it is necessary to set X20 to X24 as rotary switches so that they do not turn ON at
the same time. It is not necessary to wire unused switches, but they cannot be used for any other purpose because they
are occupied by IST instruction.
• Specify the smallest device number of practical state relays in (d1) (for the automatic mode).
• Specify the largest device number of practical state relays in (d2) (for the automatic mode).
• While the command input is ON, the following devices are automatically switched and controlled. While the command input
is OFF, the devices are not switched.
Source
Device number
(example)
Switch function
Descriptions
(s)
X20
Individual operation
Each load is turned ON and OFF by an individual pushbutton switch.
(s)+1
X21
Return to zero point
When the pushbutton switch for zero return is pressed, the machine automatically returns to
the zero point.
(s)+2
X22
Stepping
Every time the start button is pressed, the machine performs one process.
(s)+3
X23
Cycle operation
When the start button is pressed while the machine is located at the zero point, the machine
performs one cycle of automatic operation and stops at the zero point.
If the stop button is pressed in the middle of one cycle, the machine stops immediately. When
the start button is pressed after that, the machine performs the continuous operation from the
last position, and automatically stops at the zero point.
(s)+4
X24
Continuous operation
When the start button is pressed while the machine is located at the zero point, the machine
starts continuous operation.
When the stop button is pressed, the machine finishes the current cycle until the zero point,
and then stops at the zero point.
(s)+5
X25
Zero return start
Starts return to the zero point.
(s)+6
X26
Automatic start
Starts the stepping operation, cycle operation or continuous operation.
(s)+7
X27
Stop
Stops each operation.
Device number
Descriptions
ON/OFF condition
SM8040
STL transfer disable
ON condition
Always remains ON in the individual operation.
Always remains ON in the stepping operation except when the [START] button is
pressed.
Turns ON when the [STOP] button is pressed during return to the zero point and in
the cycle operation.
OFF condition
Turns OFF when the [START] button is pressed in the stepping operation.
Turns OFF after the [STOP] button is pressed during return to the zero point and in
the cycle operation.
SM8041
Transfer start
ON condition
Turns ON when the [START] button is pressed in the stepping operation and cycle
operation.
Turns ON after the [START] button is pressed in the cycle operation.
OFF condition
Turns OFF when the operation mode is changed from RUN to STOP.
Always remains OFF in the individual operation and during return to the zero point.
Turns OFF after the [STOP] button is pressed in the continuous operation.
SM8042
Start pulse
ON condition
Instantaneously turns ON when the [START] button is pressed.
OFF condition
Remains OFF except in the ON condition.
SM8043
Zero return complete
ON condition
Turns ON when return to the zero point is completed (in the user program).
OFF condition
Turns OFF when the operation mode is changed from RUN to STOP.
Remains OFF while return to the zero point is not completed.
SM8044
Zero return condition
ON condition
Turns ON when the zero point condition is established (in the user program).
OFF condition
Turns OFF when the operation mode is changed from RUN to STOP.
Remains OFF while return to the zero point is not completed.
SM8045
All output reset disable
ON condition
Turns ON when all-output reset is not executed (in the user program).
OFF condition
Turns OFF when all-output reset is executed (in the user program).
SM8046
STL state ON
ON condition
Turns ON when SM8047 (Enable STL monitoring) is ON and either step relay (device
S) is ON.
OFF condition
Turns OFF when SM8047 (Enable STL monitoring) is OFF or when SM8047 (STL
monitor enable) is ON and all step relays (device S) are OFF.
SM8047
Enable STL monitoring
ON condition
Turns ON when the IST instruction command is given.
OFF condition
Turns OFF when the step ladder is finished (in the user program).
Содержание MELSEC iQ-F FX5
Страница 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Страница 2: ......
Страница 17: ...15 CONTENTS ...
Страница 24: ...22 MEMO ...
Страница 25: ...23 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW 2 PRECAUTIONS ON PROGRAMMING ...
Страница 126: ...124 6 SEQUENCE INSTRUCTIONS 6 3 Output Instructions Operation error There is no operation error ...
Страница 132: ...130 6 SEQUENCE INSTRUCTIONS 6 3 Output Instructions Operation error There is no operation error ...
Страница 140: ...138 6 SEQUENCE INSTRUCTIONS 6 3 Output Instructions Operation error There is no operation error ...
Страница 191: ...7 BASIC INSTRUCTIONS 7 2 Arithmetic Operation Instructions 189 7 Operation error There is no operation error ...
Страница 202: ...200 7 BASIC INSTRUCTIONS 7 2 Arithmetic Operation Instructions Operation error There is no operation error ...
Страница 278: ...276 7 BASIC INSTRUCTIONS 7 4 Bit Processing Instructions Operation error There is no operation error ...
Страница 280: ...278 7 BASIC INSTRUCTIONS 7 4 Bit Processing Instructions Operation error There is no operation error ...
Страница 915: ...18 TYPE CONVERSION FUNCTIONS 18 13 Converting DWORD to WORD 913 18 Operation error There is no operation error ...
Страница 917: ...18 TYPE CONVERSION FUNCTIONS 18 14 Converting DWORD to INT 915 18 Operation error There is no operation error ...
Страница 932: ...930 18 TYPE CONVERSION FUNCTIONS 18 26 Converting DINT to WORD Operation error There is no operation error ...
Страница 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Страница 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Страница 1107: ...I 1105 MEMO ...
Страница 1111: ......