12 NETWORK COMMON INSTRUCTION
12.1 Link Dedicated Instructions
777
12
■
Control data
Device
Item
Description
Setting range
Set by
(s1)+0
Execution/error
completion type
(1) Execution type (bit 0)
• 0: No arrival acknowledgment
When the target station is in the own network: Completed when data has been sent
from the own station.
When the target station is in another network: Completed when data has arrived the
relay station of the own network.
• 1: Arrival acknowledgment used
Completed when data has been written in the target station.
(2) Error completion type (bit 7)
Specify whether to set data at completion with an error.
• 0: Do not set data in (s1)+11 and later at completion with an error.
• 1: Set data in (s1)+11 and later at completion with an error.
0000H
0001H
0080H
0081H
User
(s1)+1
Completion status
The instruction completion status is stored.
• 0: Normal
• Other than 0: Error (error code)
System
(s1)+2
Own station channel
Specify the channel to be used by own station.
1, 2
User
(s1)+3
Target station CPU type
Specify the CPU type of the target station.
• 0000H: Addressed to target station CPU (control CPU)
• 03D0H: Addressed to control system CPU
• 03D1H: Addressed to standby system CPU
• 03D2H: Addressed to system A CPU
• 03D3H: Addressed to system B CPU
• 03E0H: Addressed to multiple CPU No. 1
• 03E1H: Addressed to multiple CPU No. 2
• 03E2H: Addressed to multiple CPU No. 3
• 03E3H: Addressed to multiple CPU No. 4
• 03FFH: Addressed to target station CPU (control CPU)
0000H
03D0H to 03D3H
03E0H to 03E3H
03FFH
User
(s1)+4
Target network number
Specify the network number (1 to 239) of the target station.
1 to 239
User
b15
0
0
(2)
(1)
b7
b8
b0
…
…
Completed
Target
station
Request
source
Completed
Target
station
Request
source
Relay
station
Completed
Target
station
Request
source
Relay
station
Target
station
Completed
Содержание MELSEC iQ-F FX5
Страница 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Страница 2: ......
Страница 17: ...15 CONTENTS ...
Страница 24: ...22 MEMO ...
Страница 25: ...23 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW 2 PRECAUTIONS ON PROGRAMMING ...
Страница 126: ...124 6 SEQUENCE INSTRUCTIONS 6 3 Output Instructions Operation error There is no operation error ...
Страница 132: ...130 6 SEQUENCE INSTRUCTIONS 6 3 Output Instructions Operation error There is no operation error ...
Страница 140: ...138 6 SEQUENCE INSTRUCTIONS 6 3 Output Instructions Operation error There is no operation error ...
Страница 191: ...7 BASIC INSTRUCTIONS 7 2 Arithmetic Operation Instructions 189 7 Operation error There is no operation error ...
Страница 202: ...200 7 BASIC INSTRUCTIONS 7 2 Arithmetic Operation Instructions Operation error There is no operation error ...
Страница 278: ...276 7 BASIC INSTRUCTIONS 7 4 Bit Processing Instructions Operation error There is no operation error ...
Страница 280: ...278 7 BASIC INSTRUCTIONS 7 4 Bit Processing Instructions Operation error There is no operation error ...
Страница 915: ...18 TYPE CONVERSION FUNCTIONS 18 13 Converting DWORD to WORD 913 18 Operation error There is no operation error ...
Страница 917: ...18 TYPE CONVERSION FUNCTIONS 18 14 Converting DWORD to INT 915 18 Operation error There is no operation error ...
Страница 932: ...930 18 TYPE CONVERSION FUNCTIONS 18 26 Converting DINT to WORD Operation error There is no operation error ...
Страница 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Страница 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Страница 1107: ...I 1105 MEMO ...
Страница 1111: ......