8 APPLICATION INSTRUCTION
8.19 Initial State
629
8
• Do not program the following state relays as general state relays;
• If the devices are switched among individual operation (X20), zero return (X21) and automatic operation (X22, 23 and X24)
while the zero return complete device (SM8043) is OFF, all outputs are set to OFF. Automatic operation can be started
again after zero return is completed.
Precautions
• It is not necessary to use all switches for mode selection. When some switches are not used, leave the corresponding
numbers in the unused status. Such numbers cannot be used for any other purpose.
• The IST instruction should be programmed earlier than a series of STL circuit such as state relays S0 to S2.
• Use the state relays S10 to S19 for the zero return operation. In the final state in the zero return operation, set SM8043 to
ON, and then let it be reset to OFF by itself.
• The IST instruction can only be used once in a program.
Device number
Descriptions
ON/OFF condition
S0
Individual operation
initial state
ON condition
when a individual operation mode is selected.
OFF condition
Except a individual operation mode.
S1
Zero return initial state
ON condition
when a zero return operation mode is selected.
OFF condition
Except a zero return operation mode.
S2
Automatic operation
initial state
ON condition
when a automatic operation mode is selected.
OFF condition
Except a automatic operation mode.
Device number
Descriptions
ON/OFF condition
S0 to S9
Occupied for the initial state
• S0 to S2 are used for individual operation, zero
return and automatic operation as shown above.
• S3 to S9 can be used arbitrarily.
ON condition
Turns ON when a step relay (device S) is selected for the
initial state.
OFF condition
Turns OFF when no step relay (device S) is selected.
S10 to S19
Occupied for zero return
ON condition
Turns ON when a step relay (device S) is selected for
return to the zero point.
OFF condition
Turns OFF when no step relay (device S) is selected.
Содержание MELSEC iQ-F FX5
Страница 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Страница 2: ......
Страница 17: ...15 CONTENTS ...
Страница 24: ...22 MEMO ...
Страница 25: ...23 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW 2 PRECAUTIONS ON PROGRAMMING ...
Страница 126: ...124 6 SEQUENCE INSTRUCTIONS 6 3 Output Instructions Operation error There is no operation error ...
Страница 132: ...130 6 SEQUENCE INSTRUCTIONS 6 3 Output Instructions Operation error There is no operation error ...
Страница 140: ...138 6 SEQUENCE INSTRUCTIONS 6 3 Output Instructions Operation error There is no operation error ...
Страница 191: ...7 BASIC INSTRUCTIONS 7 2 Arithmetic Operation Instructions 189 7 Operation error There is no operation error ...
Страница 202: ...200 7 BASIC INSTRUCTIONS 7 2 Arithmetic Operation Instructions Operation error There is no operation error ...
Страница 278: ...276 7 BASIC INSTRUCTIONS 7 4 Bit Processing Instructions Operation error There is no operation error ...
Страница 280: ...278 7 BASIC INSTRUCTIONS 7 4 Bit Processing Instructions Operation error There is no operation error ...
Страница 915: ...18 TYPE CONVERSION FUNCTIONS 18 13 Converting DWORD to WORD 913 18 Operation error There is no operation error ...
Страница 917: ...18 TYPE CONVERSION FUNCTIONS 18 14 Converting DWORD to INT 915 18 Operation error There is no operation error ...
Страница 932: ...930 18 TYPE CONVERSION FUNCTIONS 18 26 Converting DINT to WORD Operation error There is no operation error ...
Страница 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Страница 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Страница 1107: ...I 1105 MEMO ...
Страница 1111: ......