Chapter 7 Peripheral Devices
7-3
7-2 Selection of circuit protectors
Use the following table to obtain the circuit protector rated current from the total rated capacity (SVJ2
total output capacity) of the motor driving the SVJ2 servo amplifier to be connected to the circuit
protector to be selected, and select the circuit protector.
When the MDS-B-SPJ2 spindle amplifier or converter unit will share circuit protectors, select from the
total circuit protector rated current of each SVJ2 total output capacity and SPJ2 spindle amplifier or
converter unit. However, separate the SVJ2 servo amplifier circuit protector from the others, and
select the NF60 type (60A) or smaller capacity dedicated for SVJ2 servo amplifiers if the total circuit
protector rated current exceeds 60A.
Circuit protector rated current table
SVJ2 total rated capacity
1.5kW or less 3.5kW or less
7kW or less
10kW or less
13kW or less
16kW or less
Circuit protector
rated current
10A 20A 30A 40A 50A 60A
MDS-B-SPJ2
MDS-B-SPJ2-02
MDS-B-SPJ2-04
MDS-B-SPJ2-075
MDS-B-SPJ2-15
MDS-B-SPJ2-22
MDS-B-SPJ2-37
MDS-B-SPJ2-55 MDS-B-SPJ2-75 MDS-B-SPJ2-110
Converter unit
MDS-A-CR-10
MDS-A-CR-15
MDS-C1-CV-37
MDS-A-CR-22
MDS-A-CR-37
MDS-C1-CV-55
MDS-A-CR-55
MDS-C1-CV-75
MDS-A-CR-75
MDS-A-CR-90
MDS-C1-CV-110
Circuit protector
rated current
10A 20A 30A 40A 50A
Circuit protector selection table
Circuit protector
rated current
10A 20A 30A 40A 50A 60A
Recommended
Circuit protector
(Mitsubishi Electric Corp.:
Option part)
NF30-CS3P
10A
NF30-CS3P
20A
NF30-CS3P
30A
NF50-CP3P
40A
NF50-CP3P
50A
NF60-CP3P
60A
The circuit protector is selected for the MDS-B-SVJ2-10 with 3 HC102 axes and an MDS-B-SPJ2-75
axis connected.
Because there are 1kW
×
3 = 3kW on the SVJ2 side, 20A is selected from the table for the circuit
protector rated current.
40A is selected from the table for the SPJ2-75 rated current.
Therefore, the total rated current is 60A, and the NF60-CP3P60A is selected.
The circuit protector is selected for the MDS-B-SVJ2-20 with 2 HC202 axes and an MDS-B-CR-90
connected.
Because there are 2kW
×
2 = 4kW on the SVJ2 side, 30A is selected from the table for the circuit
protector rated current.
50A is selected from the table for the MDS-B-CV-90 rated current.
Therefore, the total rated current is 80A. The circuit protector is separated from converter unit,
and the NF30-CS3P30A is selected for the SVJ2. (Refer to the "MDS-A/B Series Specifications
Manual" for details on selecting the converter circuit protector.)
DANGER
Install independent circuit protectors and contactors as the SVJ2 main circuit
power supply if the total current capacity exceeds 60A when the power supply
is shared between the converter and a large capacity SPJ2 spindle amplifier.
Circuit protectors may not operate for short-circuits in small capacity amplifiers
if they are shared with a large capacity unit, and this could cause fires. For the
SVJ2, use an NF60 type or lower capacity breaker.
(Example 1)
(Example 2)
Содержание MELDAS MDS-B-SVJ2 Series
Страница 1: ......
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 46: ......
Страница 92: ......
Страница 108: ......
Страница 152: ......
Страница 186: ......
Страница 194: ......
Страница 218: ......
Страница 260: ......
Страница 282: ......
Страница 283: ...12 1 Chapter 12 Inspections 12 1 Inspections 12 2 12 2 Life parts 12 2 ...
Страница 294: ......
Страница 297: ......