Chapter 6 Dedicated Options
6-3
6-1 Regenerative option
6-1-1 Combinations with servo amplifiers
Confirm the regenerative resistor capacity and possibility of connecting with the servo amplifier. Refer
to section "11-4 Selection of regenerative resistor" for details on selecting an option regenerative
resistor. The regenerative resistor generates heat, so refer to section "2-6 Connection of regenerative
resistor", and wire and install the unit while taking safety into consideration.
When using the external option regenerative resistor, install a cover on the machine, etc., so that
easily flammable items such as the cable doe not contact the detector and so that dust and oil do not
adhere onto the resistor and ignite.
Standard built-in
regenerative resistor
External option regenerative resistor type
External option
regenerative
resistor type
(Japan Resistor Mfg.)
GZG200W39OHMK
GZG200W120OHMK
3 units connected
in parallel
GZG200W39OHMK
3 units connected
in parallel
GZG300W39OHMK
3 units connected
in parallel
External option
regenerative
resistance unit type
MR-RB032
MR-RB12 MR-RB32 MR-RB30 MR-RB50
Regenerative
capacity
30W
100W
300W
300W
500W
Corresponding
servo amplifier
Resistance
value
40
Ω
39
Ω
(MR-RB12: 40
Ω
)
40
Ω
13
Ω
13
Ω
MDS-B-SVJ2-01
No built-in resistor
○
○
MDS-B-SVJ2-03 10W
100
Ω
○
○
MDS-B-SVJ2-04 10W
100
Ω
○
○
MDS-B-SVJ2-06 10W 40
Ω
○
○
○
MDS-B-SVJ2-07 20W 40
Ω
○
○
MDS-B-SVJ2-10 100W 13
Ω
○
○
MDS-B-SVJ2-20 100W 13
Ω
○
○
No. Abbrev.
Parameter
name
Explanation
SV036
PTYP Regenerative resistor type
This is a HEX setting parameter.
F
E
D
C
B
A
9
8
7
6 5 4 3 2
1
0
amp
rtyp
emgx
bit
Explanation
Set the regenerative resistor type.
Setting
value
Regenerative resistor or
regenerative resistance unit
0
Amplifier standard built-in resistor (SVJ2-01 has no
built-in resistor.)
1 Setting
prohibited
2 MR-RB032
3
MR-RB12 or GZG200W39OHMK
4
MR-RB32 or GZG200W120OHMK:
3 units connected in parallel
5
MR-RB30 or GZG200W39OHMK:
3 units connected in parallel
6
MR-RB50 or GZG300W39OHMK:
3 units connected in parallel
7 ~ F
Setting prohibited
8~B
CAUTION
1. The regenerative option and servo amplifier cannot be set to a combination
other than that designated. Failure to use the correct combination could
lead to fires.
2. Protection will not be performed correctly if the parameter setting is
incorrect. Carefully confirm the regenerative resistor type before setting the
parameter.
3. When using the external option regenerative resistor, a cover must be
installed on the machine, so that easily flammable items do not contact or
adhere onto the resistor.
Содержание MELDAS MDS-B-SVJ2 Series
Страница 1: ......
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 46: ......
Страница 92: ......
Страница 108: ......
Страница 152: ......
Страница 186: ......
Страница 194: ......
Страница 218: ......
Страница 260: ......
Страница 282: ......
Страница 283: ...12 1 Chapter 12 Inspections 12 1 Inspections 12 2 12 2 Life parts 12 2 ...
Страница 294: ......
Страница 297: ......