- 68 -
6.Other
6.5 Measurement Characteristic
■
Metering actions in other than operation mode
Status
Measurement
Display
Analog output
Alarm contact point
Pulse output
Several seconds just
after turning on the
auxiliary power supply
(Backlight is lit, and
LCD is not lit.)
No measurement
No display
Output over about
100% may be
made until internal
voltage becomes
stable.
Opened
No output
Setting mode,
Set value confirmation
mode
Password protection
mode
Same actions
as in operation
mode
No display of
measured value
Same actions
as in operation
mode
Status before
getting into setting
mode and set
value confirmation
mode is kept.
Same actions
as in operation
mode
During power failure
No measurement
No display
No output
Opened
No output
■
Metering actions in input status
Measurement
items
Actions
Current (A)
Current
demand (DA)
0A when the input current is less than 0.005A
When it is over the upper limit of the possible
display range (9999), the upper limit of the
possible display range (9999) is displayed.
Voltage (V)
0V when the input voltage (line voltage) is less than11V.
For 3-phase 4-wire, 0V when the line to neutral voltage
is less than 11V or the line to line voltage is less than
19V.
For 1-phase 3-wire, 0V when the voltage between
P1-P3 is less than 22V.
When it is over the upper limit of the possible
display range (9999), the upper limit of the
possible display range (9999) is displayed.
(Note 2)
Active power (W)
Reactive power (var)
Apparent power (VA)
0W, 0var and 0VA for total when the current and the
voltage are 0A and 0V for all 3 phases.
0W, 0var and 0VA for each phase when the current of
phase n is 0A or the voltage of phase n is 0V.
(where n = 1,2 or 3)
When it is over the upper limit of the possible
display range (9999), the upper limit of the
possible display range (9999) is displayed.
Power factor (PF)
1.0 for total when the current and the voltage are 0A and 0V for all 3 phases.
1.0 for each phase when the current of phase n is 0A or the voltage of phase n is 0V. (where n = 1,2 or 3)
Frequency (Hz)
When the voltage of phase1 is 0V, ---- is displayed.
(Note 3)
When the frequency is less than 44.5Hz or
over 99.9Hz, ---- is displayed.
Harmonic current
(HI)
For effective value measurement
: When the voltage of phase1 is 0V, 0A is displayed.
: When the frequency is less than 44.5Hz,
---- is displayed for all phases.
For content factor measurement
: When the 1st current harmonic is 0A, 0A is
displayed. (Each phase)
: When the voltage of phase1 is 0V, 0% is
displayed.
: When the frequency is less than 44.5Hz,
---- is displayed for all phases.
Harmonic Voltage
(HV)
For effective value measurement
: When the voltage of one phase is 0V, ---- is displayed.
: When the voltage is 0V, 0V is displayed. (Each phase)
: When the frequency is less than 44.5Hz,
---- is displayed for all phases.
For content factor measurement
: When the voltage of one phase is 0V, ---- is
displayed.
: When the voltage is 0V, 0% is displayed.
(Each phase)
: When the frequency is less than 44.5Hz,
---- is displayed for all phases.
Operating Time
999999 hour is displayed if it is over 999999.
Note1: Input current and input voltage means the input to the instrument. They are not to primary sides of VT, CT.
Note2: For direct measurement, it does not input upper maximum scale value.
Note3: Depending on the setting, “----“ is displayed when the voltage of phase 1 is not 0V.
■
Analog output action
Output setting
Output range
Output limit setting is “ON”
-1% to 101% of span
Output limit setting is “OFF”
-5% to 105% of span