- 33 -
3. Setting
3.8 Setting Menu 7:
Setting Periodic Active Energy, Rolling Demand, and Digital Input/Output
According to the setting flow (page 14), save the changed
contents, or continue to the other setting menu.
Setting menu
SET
DISPLAY
SET
Set “on or off” of the digital input/output display.
When the optional plug-in module is not installed,
this display will be skipped.
oFF
on
(
Not displayed
)
(
Displayed
)
⑤
Digital
input/output display
Set the method to reset the digital input.
When the optional plug-in module is not installed,
this display will be skipped.
Reset method
(
Setting value
)
Description
(For details, refer to page 57.)
Auto
(
Auto
)
When the digital input is turned to OFF
(opened), the digital input state is
automatically turned to OFF (opened).
Latch
(
HoLd
)
When the digital input detects ON (closed)
once, even if the digital input is turned to OFF
(opened), the digital input state is retained as
ON (closed) until the operation of releasing the
latch is performed.
⑥
Digital input reset
method
Note.When the ME-4210-SS96 optional plug-in module is installed, the “d.in1” set
②
Control
setting for switching time segments of periodic active energy or
④
Rolling demand time
setting, this display will be skipped.