- 30 -
3. Setting
3.7 Setting Menu 6: Setting the Analog Output
Analog output CH2-CH4 detailed setting
The setting method is the same as
②
Analog output CH1 detailed setting .
④
Analog output CH2 to CH4
detailed settings
Set the measurement item that is output to analog output CH2 to CH4.
The setting method is the same as
①
Analog output CH1 output item .
③
Analog output CH2 to CH4
measurement item
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
Analog output CH1 detailed setting
(The following setting can be made separately from the measurement items included in the
display pattern.)
(1)Set the
current / current demand / voltage / active power / reactive power /
power factor for analog output.
(Setting menu 6.1.1)
Output item
Setting range
*2
A
Demand
A
Primary Current
(1.4.1 Primary Current Setting value)
SP.(Special Setting)
V
W
var
PF
-0.5 to 1 to 0.5
-0 to 1 to 0
(2)
Set the current / current demand / active power for analog output.
(Setting menu 6.1.2)
Output item
Setting range
*2
A
Demand
A
W
Single deflection
Double deflection
②
Analog output CH1
detailed setting
*
1.
When var or PF are set as output items, it moves to the next analog
output settings.
*2. Detailed setting values are according to the values shown in the
table on pages 64 to 66.
±0 STEP (100%
:
Rating
)
~
~
-10 STEP (About 40%)
+3 STEP (About 120%)
± 0 STEP (100%
:
Rating
)
~
~
-18 STEP (About 20%)
+ 3 STEP (About 120%)
mA
4
12
20
-40kW
40kW
0
<
Double deflection
>
mA
4
20
40kW
0
<
Single deflection
>
To next CH settings
※
1
mA
4
12
20
-0.5
0.5
1
mA
4
12
20
-0
0
1
+
-
± 0 STEP
(100%
:
standard maximum scale value
)
~
~
-18 STEP (About 20%)
+10 STEP (About 250%)
+
-
+
-
SET
DISPLAY
SET