- 28 -
3.Setting
3.6 Setting Menu 5:
Pulse and Alarm Settings (Setting Upper/Lower Limit Alarm, Motor Starting Current
Mask Function, Pulse Output, etc.)
According to the setting flow (page 14), save the changed
contents, or continue to the other setting menu.
Setting menu
Set the pulse width for output pulse.
Set according to the input pulse conditions for the receiver.
In the following cases, this display will be skipped.
・
ME-4210-SS96 optional plug-in module is not installed.
・
Not set “PULSE” to
⑨
Pulse/Alarm output 1 and
⑫
Pulse/Alarm output 2.
・
Set “non” to
⑩
Pulse output 1 output item and
⑬
Pulse output 2 output item .
Note
When the pulse unit is set to the minimum value and the pulse width is set to
0.500s or 1.000s, the pulse output cannot follow if the load is too large, which
can result in a decrease in the pulse output number.
⑮
Pulse width
0.125s
0.500s
1.000s
Set a pulse unit for pulse output 2.
In the following cases, this display will be skipped.
・
ME-4210-SS96 optional plug-in module is not installed.
・
Not set “PULSE” to
⑫
Pulse/Alarm output 2.
・
Set “non” to
⑬
Pulse output 2 output item.
The setting method is the same as for
⑪
Pulse output 1 pulse unit .
(Factory default setting values: Minimum possible value for pulse unit)
⑭
Pulse output 2
pulse unit
Set the element that is output to pulse output 2.
The same elements as pulse output 1 can be set.
In the following cases, this display will be skipped.
・
ME-4210-SS96 optional plug-in module is not installed.
・
Not set “PULSE” to
⑫
Pulse/Alarm output 2.
The setting method is the same as
⑩
Pulse output 1 output item .
(Factory default setting value: Reactive energy (Imported, Lag))
⑬
Pulse output 2
output item
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
Set the output function of Pulse/Alarm output 2.
When the ME-4210-SS96 optional plug-in module is not installed,
this display will be skipped.
Please refer to page 57 for the correspondence between Alarm output
and Alarm item.
⑫
Pulse/Alarm
output 2
AL
PULSE
(
Alarm output
)
(
Pulse output
)