120
10 TROUBLESHOOTING
10.5 List of Status Codes
E479H
• The DP-Slave did not respond
to the request.
• Request is executed during
other function is operating
• Check whether request data supported by the DP-Slave are correctly configured and retry.
(Refer to the manuals for each DP-Slave)
• When the acyclic communication function is executed successively to the same DP-Slave,
adjust the execution interval and retry. (Refer to the manuals for each DP-Slave)
• Check whether the interlock between the global control function and time control of DP-
Slaves is correct and retry.
E4D0H
The specified request is invalid
Check the request code.
E4D1H to E4DBH
A hardware failure has been
detected.
Please consult your local Mitsubishi representative.
E4DCH
The same DP-Slave is the object
of another Acyclic communication
function or alarm request.
Check that execution of other Acyclic communication function and alarm requests is
completed and retry.
E4DDH
No resource is available.
Check that execution of other Acyclic communication function and alarm requests is
completed and retry.
E4DEH
Invalid parameter setting
Check the parameters and retry.
E4DFH
The DP-Slave cannot respond.
Check the wiring of PROFIBUS cables and the start completed status of the DP-Slave, and
retry. For the start completed status of DP-Slaves, refer to the manual for the DP-Slave.
E4E0H
No response was received from
the DP-Slave.
Check the status of the DP-Slave and retry.
E4E1H
The same DP-Master is executing
the following functions to the
same DP-Slave.
• Acyclic communication function
• Alarm acquisition function
Check that the processing of the following functions are completed and retry.
• Acyclic communication function
• Alarm acquisition function
E4E3H
A hardware failure has been
detected.
Please consult your local Mitsubishi representative.
E500H
Out of range the target FDL
address of DP-Slave
Check the specified FDL address and retry.
E501H
The target FDL address of DP-
Slave is for a not-configured
station.
Check the specified FDL address and retry.
E502H
The target DP-Slave is own
station (the DP-Master)
Check the specified FDL address and retry.
E503H
The target FDL address is for a
reserved station or temporarily
reserved station.
Check the specified FDL address and retry.
E504H
Invalid alarm read request code
Check the specified request code and retry.
E505H
Invalid ACK request bit
Check bits specified in Alarm request area (Un\G26434) and retry.
E506H
Alarm read request exception
response
Check detailed status codes 1 to 3 and take action.
E507H
Data are not being exchanged.
Turn on 'Data exchange start request signal' (Un\G2.b0) and retry.
E508H
An error response to an ACK
request was detected.
Check detailed status codes 1 to 3 and take action.
E510H
A physical execution error was
detected
Check detailed error codes 2 to 3 and take action.
E520H
The DP-Slave detected an invalid
parameter in the request.
Check whether request data supported by the DP-Slave are correctly configured and retry.
(Refer to the manual for each DP-Slave)
E521H
No alarm is available to the DP-
Slave.
Check whether request data supported by the DP-Slave are correctly configured and retry.
(Refer to the manual for each DP-Slave)
E530H
The alarm is not available
Check whether the DP-Slave supports the alarm and retry.
E531H
Invalid DP-Slave status
Check whether the DP-Slave is correctly executing the data exchange and retry.
E540H
Out of range the target FDL
address of DP-Slave
Check the specified FDL address and retry.
E541H
The target FDL address of DP-
Slave is for a not-configured
station.
Check the specified FDL address and retry.
E542H
The target DP-Slave is own
station (the DP-Master)
Check the specified FDL address and retry.
E543H
The target FDL address is for a
reserved station or temporarily
reserved station
Check the specified FDL address and retry.
Status code
Error details and cause
Action
Содержание FX5-DP-M
Страница 1: ...MELSEC iQ F FX5 User s Manual PROFIBUS ...
Страница 2: ......
Страница 9: ...7 MEMO ...
Страница 12: ...10 INDEX 168 REVISIONS 170 WARRANTY 171 TRADEMARKS 172 ...
Страница 13: ...11 CONTENTS ...
Страница 19: ...1 DESCRIPTION 17 1 MEMO ...
Страница 100: ...98 9 PROGRAMMING 9 2 DP Master settings DP Slave FDL address 2 ...
Страница 101: ...9 PROGRAMMING 9 2 DP Master settings 99 9 DP Slave FDL address 3 ...
Страница 108: ...106 9 PROGRAMMING 9 8 Program Example of the Global Control Function ...
Страница 109: ...9 PROGRAMMING 9 8 Program Example of the Global Control Function 107 9 ...
Страница 110: ...108 9 PROGRAMMING 9 8 Program Example of the Global Control Function ...
Страница 112: ...110 9 PROGRAMMING 9 9 Program Example of Acyclic Communication Acyclic Communication ...
Страница 114: ...112 9 PROGRAMMING 9 10 Program Example of the Alarm Acquisition Function ...
Страница 169: ...APPX Appendix 4 Processing Time 167 A MEMO ...
Страница 175: ......