122
10 TROUBLESHOOTING
10.5 List of Status Codes
E576H
No alarm is available for the ACK
request.
Check the alarm occurrence status of the specified DP-Slave and retry.
E580H
No alarm is available for the ACK
request.
Check the alarm occurrence status of the specified DP-Slave and retry.
E581H
The alarm specified in the ACK
request is not present.
Check the alarm occurrence status of the specified DP-Slave and retry.
E582H
The alarm function is deactivated
for the specified DP-Slave.
Therefore no alarm is available for
the ACK request.
Check whether the DP-Slave supports the alarm and retry.
E590H to E59AH
A hardware failure has been
detected.
Please consult your local Mitsubishi representative.
E59BH
The Acyclic communication
function is being executed for the
same DP-Slave.
Check that execution of the Acyclic communication function is completed and retry.
E59CH
No resource is available.
Check that execution of the Acyclic communication function is completed and retry.
E59DH
Invalid parameter setting
Check the parameters and retry.
E59EH
The DP-Slave cannot respond.
Check the wiring of PROFIBUS cables and the start completed status of the DP-Slave, and
retry.
When the Acyclic communication function is executed successively to the same DP-Slave,
adjust the execution interval and retry.
For the start completed status of DP-Slaves and the intervals of executing the Acyclic
communication function, refer to the following.
Manual for each DP-Slave
E59FH
No response was received from
the DP-Slave.
Check the status of the DP-Slave and retry.
E5A0H
The same DP-Master is executing
the following functions to the
same DP-Slave.
• Acyclic communication function
• Alarm acquisition function
Check that the processing of the following functions are completed and retry.
• Acyclic communication function
• Alarm acquisition function
E5A2H
A hardware failure has been
detected.
Please consult your local Mitsubishi representative.
F120H
Diagnostic information was
detected in a DP-Slave.
Check Diagnostic information area for the diagnostic information detected in the DP-Slave
and take action against the problem.
F121H
A DP-Master or DP-Slave on the
same line has the same FDL
address.
Check the FDL addresses for the DP-Master and DP-Slave and then configure them with the
different FDL addresses.
F122H
An error was detected on the line.
Or the master parameters are
inappropriate.
Check wiring of bus terminators and PROFIBUS cables.
When the bus terminators and PROFIBUS cables are wired correctly, increase setting value
"Min. slave interval" of the master parameters.
F123H
An error was detected on the line.
Or the master parameters are
inappropriate.
Check wiring of bus terminators and PROFIBUS cables.
When the bus terminators and PROFIBUS cables are wired correctly, increase setting value
"Min. slave interval" of the master parameters.
F124H
An error was detected on the line.
Or the master parameters are
inappropriate.
Check wiring of bus terminators and PROFIBUS cables.
When the bus terminators and PROFIBUS cables are wired correctly, increase setting value
"Min. slave interval" of the master parameters.
F125H
The DP-Master is in the clear
request sent state.
Since master parameter "Error action flag" is checked, clear requests are being sent to all
the DP-Slaves.
When clear requests do not need sending, uncheck "Error action flag".
F126H
The line status is unstable.
Or the PROFIBUS cable has
short-circuited.
Check wiring of bus terminators and PROFIBUS cables.
Check whether the PROFIBUS cable has short-circuited.
Status code
Error details and cause
Action
Содержание FX5-DP-M
Страница 1: ...MELSEC iQ F FX5 User s Manual PROFIBUS ...
Страница 2: ......
Страница 9: ...7 MEMO ...
Страница 12: ...10 INDEX 168 REVISIONS 170 WARRANTY 171 TRADEMARKS 172 ...
Страница 13: ...11 CONTENTS ...
Страница 19: ...1 DESCRIPTION 17 1 MEMO ...
Страница 100: ...98 9 PROGRAMMING 9 2 DP Master settings DP Slave FDL address 2 ...
Страница 101: ...9 PROGRAMMING 9 2 DP Master settings 99 9 DP Slave FDL address 3 ...
Страница 108: ...106 9 PROGRAMMING 9 8 Program Example of the Global Control Function ...
Страница 109: ...9 PROGRAMMING 9 8 Program Example of the Global Control Function 107 9 ...
Страница 110: ...108 9 PROGRAMMING 9 8 Program Example of the Global Control Function ...
Страница 112: ...110 9 PROGRAMMING 9 9 Program Example of Acyclic Communication Acyclic Communication ...
Страница 114: ...112 9 PROGRAMMING 9 10 Program Example of the Alarm Acquisition Function ...
Страница 169: ...APPX Appendix 4 Processing Time 167 A MEMO ...
Страница 175: ......