APPX
Appendix 3 Buffer Memory
143
A
Slave status area (Reserved station setting status)
■
Slave status area (Reserved station setting) (Un\G23048 to Un\G23051)
This area stores reserved station settings or temporarily reserved station settings for DP-Slaves. (
Reserved Station Specification Function)
• 0: Normal DP-Slave or not-configured station
• 1: Reserved station setting or temporarily reserved station setting
The values in the table indicate which number of DP-Slave each bit represents.
Slave status area (Diagnostic information detection)
■
Slave status area (Diagnostic information detection) (Un\G23056 to Un\G23060)
This area stores diagnostic information generation status of DP-Slaves. (
Page 25 Acquisition of diagnostic information
and extended diagnostic information)
Turning on 'Data exchange start request signal' (Un\G2.b0) clears all the information in 'Slave status area (Diagnostic
information detection)' (Un\G23056 to Un\G23060).
The values in the table indicate which number of DP-Slave each bit represents.
Local station error information area
■
Local station error information area (Un\G23071)
This area stores the error information on own station (FX5-DP-M).
The information in 'Local station error information area' (Un\G23071) is not cleared by resolving the problem
that occurred to the FX5-DP-M.
To clear the information in 'Local station error information area' (Un\G23071), turn on 'Diagnostic information
area clear request signal' (Un\G2.b2).
Address
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
Un\G23048
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Un\G23049
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
Un\G23050
48
47
46
45
44
43
42
41
40
39
38
37
36
35
34
33
Un\G23051
64
63
62
61
60
59
58
57
56
55
54
53
52
51
50
49
Address
Name
Description
Initial
value
Un\G23056
All stations'
diagnostic
status
Stores the diagnostic information detection status of all the DP-Slaves.
When a diagnostic information has detected even on one DP-Slave in 'Each station's diagnostic status'
(Un\G23057 to Un\G23060), 1 is stored in 'All stations' diagnostic status' (Un\G23056).
• 0: All DP-Slaves are operating normally
• 1: Diagnostic error information detected
0000H
Un\G23057 to
Un\G23060
Each station's
diagnostic
status
Stores the diagnostic information detection status of each DP-Slave.
• 0: Normal (including reserved stations, temporarily reserved stations, and not-configured stations)
• 1: Diagnostic error information has been detected
0000H
Address
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
Un\G23057
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Un\G23058
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
Un\G23059
48
47
46
45
44
43
42
41
40
39
38
37
36
35
34
33
Un\G23060
64
63
62
61
60
59
58
57
56
55
54
53
52
51
50
49
Address
Stored value
Description
Un\G23071
0000H
Normal
Other than
0000H
Error (
Содержание FX5-DP-M
Страница 1: ...MELSEC iQ F FX5 User s Manual PROFIBUS ...
Страница 2: ......
Страница 9: ...7 MEMO ...
Страница 12: ...10 INDEX 168 REVISIONS 170 WARRANTY 171 TRADEMARKS 172 ...
Страница 13: ...11 CONTENTS ...
Страница 19: ...1 DESCRIPTION 17 1 MEMO ...
Страница 100: ...98 9 PROGRAMMING 9 2 DP Master settings DP Slave FDL address 2 ...
Страница 101: ...9 PROGRAMMING 9 2 DP Master settings 99 9 DP Slave FDL address 3 ...
Страница 108: ...106 9 PROGRAMMING 9 8 Program Example of the Global Control Function ...
Страница 109: ...9 PROGRAMMING 9 8 Program Example of the Global Control Function 107 9 ...
Страница 110: ...108 9 PROGRAMMING 9 8 Program Example of the Global Control Function ...
Страница 112: ...110 9 PROGRAMMING 9 9 Program Example of Acyclic Communication Acyclic Communication ...
Страница 114: ...112 9 PROGRAMMING 9 10 Program Example of the Alarm Acquisition Function ...
Страница 169: ...APPX Appendix 4 Processing Time 167 A MEMO ...
Страница 175: ......