4. SSCNET COMMUNICATION STATUS

When the inverter is fitted with the SSCNET communication unit (FR-V5NS) and has any of station No. 0 to No. 7, pow-
ering it on places it in the SSCNET communication initialization waiting status. In this status, the inverter is put in the
SSCNET operation mode and cannot be switched to the external or PU operation mode. In addition, the Pr. 79 "opera-
tion mode selection" setting is disabled. How SSCNET communication is performed is shown below.
The status of communication with the motion controller can be monitored as a communication status.
To monitor it, set "39" (communication status) in Pr. 52 "DU/PU main display data selection". (Refer to page 16.)

*1.

The inverter is put in the SSCNET operation mode.

*2.

In the part #, the axis number appears.
("21" appears when the station number is 0.)

*3.

To reset the alarm, the alarm reset signal from the SSC-
NET or the RES terminal is valid.
A power-on reset recovers the inverter from the alarm in 
the initialization waiting status.

*4.

When communication is interrupted, an inverter reset (CF 
alarm) or inverter alarm (E.OP3) occurs.
To select alarm output presence/absence and stop opera-
tion, use Pr. 499 "action selection at SSCNET communica-
tion interruption". (Refer to page 16.)

*5.

If the motion controller is powered off during inverter power 
input, the inverter is placed in the initialization waiting sta-
tus.

SSCNET communication status

13

Motion controller 

power-off

Inverter power-on

Motion controller 

power-on

Inverter alarm 
(outside initial 

parameter range)

Alarm reset

Ready off/servo off

Waiting for initial communication

Initial communication start

Initial communication 

parameter setting

Initial communication end

Ready on/servo off

Ready on/servo on

Communication shutoff

(*2)

Emergency stop

Cancel

12

Alarm 
code

14

99

E.9

2#

3#

4#

99

E.OP3

88

(*2)

(*2)

(*3)

(*5)

(*4)

(*1)

11

CF alarm

Waiting for initial communication

#: Axis number

Communica-

tion Status

Description

0

The V5NS is not fitted or the station number is F

11

After SSCNET communication had been estab-
lished, the motion controller powered off.

12

Immediately after the inverter has been powered 
on, it is waiting for motion controller power-on 
and initial communication.

13

Initialization communication start

14

The initial parameters are being received during 
initialization.

2#

Ready off was received.

3#

Servo off was received.

4#

Servo on was received.

88

Emergency stop (inverter output shutoff)

99

Inverter trip

Содержание FR-V5NS

Страница 1: ......

Страница 2: ......

Страница 3: ......

Страница 4: ......

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ......

Отзывы: