- 5 -

- 5 -

Screen

Operation

Note

5-2.

1

Push the

 

 

or

 

 

key,

 

and select the display mode.

2

Push the

 

    / Phase    key.

3

Transition to the following screen by the selection of measurement mode.

[Wh+A+4] setting   

To 5-3

[Harmonics] setting

 To 5-4

[DISP.Mode]

Wh+A+4

Harmonics

*In  case  of  the  model  EMU4-BM1-MB  ,  the 

Harmonics” not be displayed.

 

Wh+A+4…In addition to the active energyand current,

up to 4 items can bedisplayed by selection.

(The harmonics data is only about total.)

Harmonics…It can display aboutharmonic data

at each order.

 

5-3.

1

 

Push the   

    or   

    key,

 

and move the cursor to target element.

In the actual display, it will be scrolling display of each three elements

in one screen.

2

Push the   

    or   

    key, and choose the selected or desselected.

3

When selecting the other measurement item, repeat the operation from 

1

to 

2

.

4

Push the    /Phase key, and determine the setting.

5

Transition to the following screen by the selection of measurement mode.

Not check 

HA

and

HV

To 5-1

Check 

HA

or 

HV

         

To 5-4

[Element]

V, W, var, VA, PF, Hz, CONV.Wh, PRD.Wh, 

OP.Time, REG.Wh, varh, CONV.PLS, UNB.V, HA, HV

 

Deselected

,

Selected

 

 

*The  selectable  number  of  elements is  up  to 4.  So, 

change the selection at the statethat already 4 items 

are selected, deselectthe items before changing. 

* Elements can't select in follow table.

Element

In the case can not select 

UNB.A

UNB.V

In  the  case  of  setting  simplicity 

measuring mode

 

Periodic 

Wh

In  the  case  of  EMU4-BM1-MB,

EMU4-A2, EMU4-VA2.

External input is not contact input.

 

Pulse

In the case EMU4-BM1-MB,

EMU4-A2, EMU4-VA2.

Pulse input is not contact input.

 

HA

HV

In the case EMU4-BM1-MB.

 

VA

In the case EMU4-BM1-MB,

Wiring is 1P2W,1P3W or 3P3W

 

Wh

converted

value

 

In the case EMU4-BM1-MB

 

 

*Elements is showed follow.

V

Voltage

W

Electric power

var

reactive power

VA

apparent power

PF

Power factor

Hz

frequency

Wh converted value

Electric energy (converted)

Periodic Wh

Electric energy (regeneration)

Regenerated Wh

Periodic electric energy

varh

Reactive energy (consumption lag)

PULSE

Pulse count value and pulse converted value

UNB.A

Current unbalance rate

UNB.V

Voltage unbalance rate

HA

Harmonics current

HV

Harmonics voltage

5-4.

1

 

Push the   

    or   

    key

 

, and change the 

HA,HV

value.

2

Push the

 

    / Phase    key.

3

5-1 will be displayed.

[HA,HV]

r.m.s.

*

 

In case of the model EMU4-BM1-MB,

HA,HV

 

can 

not be set.

   

r.m.s.… to display the RMS value of harmonic current

or harmonic voltage.

The “%” not be displayed.

%… to display the distortion rate and content rate of 

harmonic current or harmonic voltage.

The “r.m.s.”

 

not be displayed.

 

6(1) Setup the measurement mode 

EMU4-LG1-MB only

6

(

1

)

-1.

1

In 6(1)-1,

 

push the   

    or   

    key, and move the cursor to the

“5 MEA.Mode”.

2

Push the

   

    / Phase    key.

3

6(1)-2 will be displayed.

 

Setup the measurement mode of “Io” or ”Ior”.

6

(

1

)

-2.

1

 

Push the     

    or   

    key, and select the measurement mode.

2

 

Push the

   

/ Phase    key.

3

6(1)-1 will be displayed.

[MEA.Mode]

High SENS.

Low SENS.

Low SENS.…0

1000mA1mAstep

High SENS.…0.00

100mA

 

0.01mAstep

6(2) Setup the measurement mode 

EMU4-AX4 only

6

(

2

)

-1.

1

In 6(2)-1,

 

push the   

    or   

    key, and move the cursor to the

“5 MEA.Mode”.

2

Push the

   

    / Phase    key.

3

6(2)-2 will be displayed.

 

Setup the measurement mode of AD converted.

6

(

2

)

-2.

1

 

Push the     

    or   

    key, and select the measurement mode.

2

 

Push the

   

/ Phase    key.

3

6(2)-1 will be displayed.

[MEA.Mode]

50ms SAMP.

1ms SAMP.

50ms SAMP.…AD converted in a cycle of 50ms.

1ms SAMP.…AD converted in a cycle of 1ms.

7(1) Setup the demand time

EMU4-BM1-MB

EMU4-HM1-MB

EMU4-A2

EMU4-VA2

7

(

1

)

-1.

1

In 7-1, push the   

    or   

    key, and move the cursor to the “6 Demand”.

2

Push the

   

    / Phase    key.

3

7(1)-2 will be displayed.

[Demand]

0sec

10sec

20sec

30sec

40sec

50sec

1min

2min

3min

4min

5min

6min

7min

8min

9min

10min

11min

12min

13min

14min

15min

20min

25min

30min

7

(

1

)

-2.

1

Push the   

    or   

    key, and move the cursor to the A

Current

.

2

Push the   

    or   

key, and change the demand time value.

3

Push the   

    or   

    key, and move the cursor to the W

Electric power

.

4

Push the   

    or   

key, and change the demand time value.

5

Push the

 

    / Phase    key

 

, and confirm the setting value.

6

7(1)-1 will be displayed.

[DISP.Mode]

Wh+A+4

Harmonics

[Measure]

3

 

A rate

4

 

DISP.Mode

5

 

MEA.Mode

[MEA.Mode]

High SENS.

Low SENS.

[HA,HV]

r.m.s.

[Measure]

4

 

DISP.Mode

5

 

MEA.Mode

6

 

Demand

[Demand]

A

2min

W

2min

[Element]

V

W

var

VA

 

PF

 

Hz

 

CONV.Wh

 

PRD.Wh

 

OP.Time

REG.Wh

 

varh

 

PLS

 

UNB.A

 

UNB.V

 

HA

 

HV

 

[Measure]

3

 

A rate

4

 

DISP.Mode

5

 

MEA.Mode

[MEA.Mode]

50ms SAMP.

1ms SAMP.

Содержание EMU4-D65

Страница 1: ...ollowing setup is need before using EMU4 D65 The one always in one system is the Master set Other display unit of please to Slave configuration The wrong setting and it does not work 3 3 Installation and connection Before installing and connecting the unit read the instruction manual without fail For safety the unit shall be installed and connected by experts in electrical work When threading and ...

Страница 2: ...uit LED A circuit number on display lights up Moreover LED of the circuit number blinks at the time of alarm occuring OUT 1 Connector Use for connection with a next display unit OUT 2 Connector Use for connection with a next display unit IEC rail attachment Use when installating on IEC rail Master LED The light is switched on at the time of operation key Change of display item and selection of a m...

Страница 3: ...antaneous power failure alarm Setup for the condition of monitoring breaker alarm Monitoring for measurement data Please refer to the instruction manual Detailed edition Please refer to the instruction manual Detailed edition Reset the Max Min data and alarm data Preset the value of Wh and varh Setup Setup Reset Set Connection test Pulse output test Alarm output test Communication test Test mode i...

Страница 4: ...key and change the set value 2 Push the Phase key and confirm the setting value 3 3 6 will be displayed 3 6 1 Push the key and change the set value 2 Push the Phase key and confirm the setting value 3 3 1 will be displayed 4 Setup the primary current All models except for EMU4 LG1 MB EMU4 PX4 and EMU4 AX4 4 1 1 In 4 1 Push the and move the cursor to the 3 A rate 2 Push the Phase key 3 4 2 will be ...

Страница 5: ...ate UNB V Voltage unbalance rate HA Harmonics current HV Harmonics voltage 5 4 1 Push the or key and change the HA HV value 2 Push the Phase key 3 5 1 will be displayed HA HV r m s In case of the model EMU4 BM1 MB HA HV can not be set r m s to display the RMS value of harmonic current or harmonic voltage The not be displayed to display the distortion rate and content rate of harmonic current or ha...

Страница 6: ...ase key and confirm the setting value 3 9 1 will be displayed 10 Setup the Simple measurement All models except for EMU4 LG1 MB EMU4 PX4 and EMU4 AX4 10 1 1 In 10 1 push the or key and move the cursor to the 9 SimpleMEA 2 Push the Phase key 3 10 2 will be displayed 10 2 1 Push the or key and select SimpleMEA On Off 2 Push the Phase key and confirm the setting value 3 Transition to the following sc...

Страница 7: ...ush the key and change the number of moving average 2 Push the Phase key and confirm the setting value 3 12 9 will be displayed 12 9 1 Push the key and change the upper limit lower limit and unit 2 Push the Phase key and confirm the setting value 3 12 10 will be displayed 12 10 1 Push the or key and select the AD converted On Off 2 Push the Phase key and confirm the setting value 3 Transition to t...

Страница 8: ...ill be displayed 13 2 4 1 Push the or key and select the multiplying factor displayed 2 Push the Phase key 3 13 2 5 will be displayed 13 2 5 1 Push the or key and select the multiplying factor displayed 2 Push the Phase key 3 13 2 1 will be displayed 14 Save the settings 14 1 14 2 1 After setting all of the items and push the Setup key 2 14 1 will be displayed 3 When save the settings push the or ...

Страница 9: ...setting To 2 6 Contact setting To 2 7 2 6 1 Push the key and change the CONV Rate value and unit 2 Push the Phase key and confirm the setting value 3 2 8 will be displayed 2 7 1 Push the or key and select thereset mode 2 Push the Phase key 3 2 8 will be displayed 2 8 1 Push the or key and select the input method Non Contact Pulse 2 Push the Phase key 3 Transition to the following screen by the set...

Страница 10: ...tput EMU4 HM1 MB EMU4 A2 EMU4 VA2 EMU4 PX4 EMU4 AX4 I O 1 Input 2 OP Time 3 Output OP Time Off 1 OP Time Mode A 1 OP Time Off 2 OP Time Mode A 2 Model EMU4 PX4 or 2 circuits measuring only 2 circuits measuring only OP Time Off 3 OP Time Off 4 4 1 1 In 4 1 Push the or key and move the cursor to the 3 Output 2 Push the Phase key 3 4 2 will be displayed EMU4 HM1 MB EMU4 A2 EMU4 VA2 Output Non Pulse A...

Страница 11: ...1 MB EMU4 LG1 MB 3 1 1 In 3 1 Push the or key and move the cursor to the 2 Baut rate 2 Push the Phase key 3 3 2 will be displayed Baut rate 2400 4800 9600 19200 38400 3 2 1 Push the or key and select the baut rate 2 Push the Phase key 3 3 1 will be displayed 4 Setup the parity EMU4 BM1 MB EMU4 HM1 MB EMU4 LG1 MB 4 1 1 In 4 1 Push the or key and move the cursor to the 3 Parity 2 Push the Phase key ...

Страница 12: ...ng all of the items push the or key and move the cursor to the OK 7 Push the Phase key and clock setting changed Note 2 8 2 2 will be displayed 9 When to exit the clock setup push the or key and move the cursor to the OK and push the Phase key If select the Cancel return to 1 1 10 After completing the settings saving and 1 1 will be displayed Year 00 01 02 13 99 Month 01 02 03 04 12 Day 01 02 29 3...

Страница 13: ...ring 2 Push the Phase key 3 2 2 will be displayed Wiring 1P2W 1P3W 3P3W 3P4W 3P4W setting is EMU2 RD 4W only 3P4W fixed 2 4 C In the case of the model MDU2 displays all 1P2W 3P4W but can not be set for 3P4W in the case of connection breaker 3 pole products 2 2 1 Push the or key and change the set value 2 Push the Phase key and confirm the setting value 3 2 1 will be displayed 3 Setup the primary v...

Страница 14: ...2kW Wfull 120kW 0 01 0 1 1 10 120kW Wfull 1200kW 0 1 1 10 100 1200kW Wfull 12000kW 1 10 100 1000 12000kW Wfull 120000kW 10 100 1000 10000 120000kW Wfull 100 1000 10000 100000 7 2 1 Push the or key and change the set value 2 Push the Phase key and confirm the setting value 3 7 1 will be displayed 8 Setup 1 3Change MDU2 8 1 1 In 8 1 Push the or key and move the cursor to the 7 1 3Change 2 Push the P...

Страница 15: ...ote 1 Transition to the setup mode 1 1 1 Push the Setup key in operation mode 2 1 1 will be displayed 1 In 1 1 Push the or key and move the cursor to the 3 Display 2 Push the Phase key 3 2 1 will be displayed 2 Setup the LCD contrast 2 1 1 Push the or key and move the cursor to the 1 Contrast 2 Push the Phase key 3 2 2 will be displayed Contrast 2 2 1 Push the or key and change the LCD contrast va...

Страница 16: ... for between the display unit connection Model EMU2 CB1 DP 10 Warranty If you have any questions or the product is broken down contact our sales representative near you The charge free warranty is effective until the earlier of 1 year after the date of your purchase or 18 months after manufacturing Repair shall be charged for the case failures occur due to your intent or fault even during the char...

Отзывы: