background image

- 4 -

7.2 Setup about rating, clock and display unit in the case of the model to connect the EMU4-**. (Setup mode)

7.2.1 Measuring setup … Setup the measuring condition of the energy measurement unit that is connected.  EMU4-PX4 is not set.

Screen

Operation

Note

1 Transition to the setup mode

1-1.

1

Push the

 

Setup

 

key in operation mode

2

1-1 will be displayed. 

 

1

Confirm that the cursor focuses the “1 Measure”, 

and push the

 

    / Phase

 

key.

2

2-1 will be displayed

 

2 Setup the phase wire system

All models except forEMU4-PX4 and EMU4-AX4

2-1.

1

In 2-1, push the

 

 

or

 

 

key, and move the cursor to the “1 Wiring”

2

 

Push the

     

/ Phase key.

3

 

2-2 will be displayed.

 

 

2-2.

1

Push the

or

key, and change the set value.

2

Push the

   

    / Phase    key, and confirm the setting value. 

3

 

2-1 will be displayed.

 

[Wiring]

1P2W

1P3W

3P3W

*If  the  basic unit  is  EMU4-BM1-MB,

 

[Wiring] will be

1P2W, 1P3W, 3P3W only.

3P4W

*The setting value is set in same voltage system after 

confirmed setting value.

 

2-3.

1

 

Push the

or

key, and change the set value.

2

Push the

   

    / Phase    key, and confirm the setting value. 

3

 

2-1 will be displayed.

[2 circuits Measuring existence]

No

Yes

*The setting value is set in same voltage system after 

confirmed setting value.

3 Setup the primary voltage

All models except for EMU4-LG1-MB, EMU4-PX4 and EMU4-AX4

3-1.

1

In 3-1,

 

push the   

, and move the cursor to the

2

 

V rate

.

2

Push the

     

/ Phase    key.

3

3-2 will be displayed.

 

*The setting value is set in same voltage system after 

confirmed setting value.

[VT]

No

 

*1P3W is 

No

fixed.

Yes

P2W, 3P3W ----------------------------------

When [VT]

No

setting

[Direct V]

110V

220V

*If the basic unit is EMU4-BM1-MB,

 

[Direct V]

 

will be

110V,220V only.

440V*

When [VT]

Yes

setting

[Primary V]

440V

6600V

11000V

13200V

13800V

690V

1100V

2200V

3300V

15000V

16500V

22000V

24000V

33000V

66000V

77000V

110000V

SP

3-2.

1

Push the     

    or   

    key, and select the VT use or non-use.

2

Push the

     

/ Phase    key.

3

Transition to the following screen by the selection of VT use or non-use

[No] setting

To 3-3

[YES] setting

To 3-4

If Wiring is 3P4W,

 

transition to 3-5

3-3.

1

Push the   

    or   

    key, and change the set value.

2

 

Push the

   

/ Phase    key, and confirm the setting value.

3

3-1 will be displayed.

     

3-4.

1

Push the   

or   

key, and change the set value.

2

Push the

   

    / Phase    key, and confirm the setting value.

3

transition to the following screen by the setting value of the primary voltage

[SP] setting

To 3-5

Non-[SP] setting

To 3-1

3-5.

1

Push the   

key, and change the set value.

2

Push the

   

    / Phase    key, and confirm the setting value.

3

3-6 will be displayed.

3-6.

1

Push the

key, and change the set value.

2

Push the

 

    / Phase    key, and confirm the setting value.

3

3-1 will be displayed.

4 Setup the primary current 

All models except for EMU4-LG1-MB, EMU4-PX4 and EMU4-AX4

4-1.

1

In 4-1,

 

Push the   

, and move the cursor to the

3 A rate

.

2

Push the

 

    / Phase    key.

3

4-2 will be displayed.

[Sensor]

Direct

5A

When “Direct” setting

[PRI A]

50A

100A

When “5A” setting 

250A

400A

600A

[PRI A]

5A

6A

7.5A

8A

10A

12A

15A

20A

25A

30A

40A

50A

60A

75A

80A

100A

250A

300A

400A

500A

600A

120A

150A

200A

750A

800A

1000A

1200A

1250A

1500A

1600A

2000A

2500A

3000A

4000A

5000A

6000A

7500A

8000A

10000A

12000A

20000A

25000A

30000A

SP

[SP.PRI.A] 

5.0

30000A

100A

10A less than, the upper two digits.

10A or more is possible to set the upper three digits.

 

4-2.

1

Push the   

and

 

move the cursor to the

Sensor

side.

2

Push the   

    or

or

    key, and select sensor type.

3

Push the   

and move the cursor to the

PRI A

side.

4

Push the   

    or   

key, 

key, 

and change the primary current value.

5

Push the

   

    / Phase    key, and confirm the setting value.

6

Transition  to  the  following  screen  by  the  setting  wiring type and primary 

current value.

      [SP]

 

setting

To 4-3

Non-[SP] setting

To 4-1

4-3.

1

Push the     

   

    key, and change the set value.

2

Push the

   

    / Phase    key, and confirm the setting value.

3

4-1 will be displayed.

5 Setup the display mode

All models except for EMU4-LG1-MB, EMU4-PX4 and EMU4-AX4

5-1.

1

 

In 5-1, push the     

  or          key, and move the cursor to the

“4

 

DISP.Mode”.

2

Push the

 

    / Phase    key.

3

5-2 will be displayed.

Set the measurement elements to be displayed in the 

display unit.

[Setup]

1

 

Measure

2

 

I/O

3

 

COM.

[Measure]

1

 

Wiring

2

 

V rate

3

 

A rate

[Wiring]

3P3W

[VT]

No

[Direct V]

220V

[Primary V]

440V

         

[SP.PRI.V]

0

00440V

[SP.2nd.V]

2

20V

[Measure]

1

 

Wiring

2

 

V rate

3

 

A rate

[Sensor]

Direct

[PRI A]

100A              [1]

[SP.PRI.A]

0

01000A

             

[1]

[Measure]

1

 

Wiring

2

 

V rate

3

 

A rate

1P2W only

[Measure]

2

 

V rate

3

 

A rate

4

 

DISP.Mode

[2 circuits 

MEA.]

Off

or

key, 

or

key 

or

key 

When [Primary V]

 

settingand SP setting

[SP.PRI.V]

1

110000V

440V

1

99V:Can be set in the 1V step.

100

110000V:Can be set in the 100V step.

[SP.2nd.V]

1

220V

110V

Can be set in the 1V step.

1P3W ----------------------------------------

“No” fixed

[Direct V]

110V

220V*

*If the basic unit is EMU4-BM1-MB, [Direct V] will be 

110V

3P4W

 

---------------------------------------

When [VT]

Yes

setting

[Direct  V]

63.5V

100V

105V

110V

115V

120V

127V

200V

220V

230V

240V

242V

250V

254V

265V

277V

When [VT]

Yes

setting

[SP.PRI.V]

1

63500V

440V

1

99V:Can be set in the 1V step.

100

63500V:Can be set in the 100V step.

[SP.2nd.V]

1

220V

64V

Can be set in the 1V step.

Содержание EMU4-D65

Страница 1: ...ollowing setup is need before using EMU4 D65 The one always in one system is the Master set Other display unit of please to Slave configuration The wrong setting and it does not work 3 3 Installation and connection Before installing and connecting the unit read the instruction manual without fail For safety the unit shall be installed and connected by experts in electrical work When threading and ...

Страница 2: ...uit LED A circuit number on display lights up Moreover LED of the circuit number blinks at the time of alarm occuring OUT 1 Connector Use for connection with a next display unit OUT 2 Connector Use for connection with a next display unit IEC rail attachment Use when installating on IEC rail Master LED The light is switched on at the time of operation key Change of display item and selection of a m...

Страница 3: ...antaneous power failure alarm Setup for the condition of monitoring breaker alarm Monitoring for measurement data Please refer to the instruction manual Detailed edition Please refer to the instruction manual Detailed edition Reset the Max Min data and alarm data Preset the value of Wh and varh Setup Setup Reset Set Connection test Pulse output test Alarm output test Communication test Test mode i...

Страница 4: ...key and change the set value 2 Push the Phase key and confirm the setting value 3 3 6 will be displayed 3 6 1 Push the key and change the set value 2 Push the Phase key and confirm the setting value 3 3 1 will be displayed 4 Setup the primary current All models except for EMU4 LG1 MB EMU4 PX4 and EMU4 AX4 4 1 1 In 4 1 Push the and move the cursor to the 3 A rate 2 Push the Phase key 3 4 2 will be ...

Страница 5: ...ate UNB V Voltage unbalance rate HA Harmonics current HV Harmonics voltage 5 4 1 Push the or key and change the HA HV value 2 Push the Phase key 3 5 1 will be displayed HA HV r m s In case of the model EMU4 BM1 MB HA HV can not be set r m s to display the RMS value of harmonic current or harmonic voltage The not be displayed to display the distortion rate and content rate of harmonic current or ha...

Страница 6: ...ase key and confirm the setting value 3 9 1 will be displayed 10 Setup the Simple measurement All models except for EMU4 LG1 MB EMU4 PX4 and EMU4 AX4 10 1 1 In 10 1 push the or key and move the cursor to the 9 SimpleMEA 2 Push the Phase key 3 10 2 will be displayed 10 2 1 Push the or key and select SimpleMEA On Off 2 Push the Phase key and confirm the setting value 3 Transition to the following sc...

Страница 7: ...ush the key and change the number of moving average 2 Push the Phase key and confirm the setting value 3 12 9 will be displayed 12 9 1 Push the key and change the upper limit lower limit and unit 2 Push the Phase key and confirm the setting value 3 12 10 will be displayed 12 10 1 Push the or key and select the AD converted On Off 2 Push the Phase key and confirm the setting value 3 Transition to t...

Страница 8: ...ill be displayed 13 2 4 1 Push the or key and select the multiplying factor displayed 2 Push the Phase key 3 13 2 5 will be displayed 13 2 5 1 Push the or key and select the multiplying factor displayed 2 Push the Phase key 3 13 2 1 will be displayed 14 Save the settings 14 1 14 2 1 After setting all of the items and push the Setup key 2 14 1 will be displayed 3 When save the settings push the or ...

Страница 9: ...setting To 2 6 Contact setting To 2 7 2 6 1 Push the key and change the CONV Rate value and unit 2 Push the Phase key and confirm the setting value 3 2 8 will be displayed 2 7 1 Push the or key and select thereset mode 2 Push the Phase key 3 2 8 will be displayed 2 8 1 Push the or key and select the input method Non Contact Pulse 2 Push the Phase key 3 Transition to the following screen by the set...

Страница 10: ...tput EMU4 HM1 MB EMU4 A2 EMU4 VA2 EMU4 PX4 EMU4 AX4 I O 1 Input 2 OP Time 3 Output OP Time Off 1 OP Time Mode A 1 OP Time Off 2 OP Time Mode A 2 Model EMU4 PX4 or 2 circuits measuring only 2 circuits measuring only OP Time Off 3 OP Time Off 4 4 1 1 In 4 1 Push the or key and move the cursor to the 3 Output 2 Push the Phase key 3 4 2 will be displayed EMU4 HM1 MB EMU4 A2 EMU4 VA2 Output Non Pulse A...

Страница 11: ...1 MB EMU4 LG1 MB 3 1 1 In 3 1 Push the or key and move the cursor to the 2 Baut rate 2 Push the Phase key 3 3 2 will be displayed Baut rate 2400 4800 9600 19200 38400 3 2 1 Push the or key and select the baut rate 2 Push the Phase key 3 3 1 will be displayed 4 Setup the parity EMU4 BM1 MB EMU4 HM1 MB EMU4 LG1 MB 4 1 1 In 4 1 Push the or key and move the cursor to the 3 Parity 2 Push the Phase key ...

Страница 12: ...ng all of the items push the or key and move the cursor to the OK 7 Push the Phase key and clock setting changed Note 2 8 2 2 will be displayed 9 When to exit the clock setup push the or key and move the cursor to the OK and push the Phase key If select the Cancel return to 1 1 10 After completing the settings saving and 1 1 will be displayed Year 00 01 02 13 99 Month 01 02 03 04 12 Day 01 02 29 3...

Страница 13: ...ring 2 Push the Phase key 3 2 2 will be displayed Wiring 1P2W 1P3W 3P3W 3P4W 3P4W setting is EMU2 RD 4W only 3P4W fixed 2 4 C In the case of the model MDU2 displays all 1P2W 3P4W but can not be set for 3P4W in the case of connection breaker 3 pole products 2 2 1 Push the or key and change the set value 2 Push the Phase key and confirm the setting value 3 2 1 will be displayed 3 Setup the primary v...

Страница 14: ...2kW Wfull 120kW 0 01 0 1 1 10 120kW Wfull 1200kW 0 1 1 10 100 1200kW Wfull 12000kW 1 10 100 1000 12000kW Wfull 120000kW 10 100 1000 10000 120000kW Wfull 100 1000 10000 100000 7 2 1 Push the or key and change the set value 2 Push the Phase key and confirm the setting value 3 7 1 will be displayed 8 Setup 1 3Change MDU2 8 1 1 In 8 1 Push the or key and move the cursor to the 7 1 3Change 2 Push the P...

Страница 15: ...ote 1 Transition to the setup mode 1 1 1 Push the Setup key in operation mode 2 1 1 will be displayed 1 In 1 1 Push the or key and move the cursor to the 3 Display 2 Push the Phase key 3 2 1 will be displayed 2 Setup the LCD contrast 2 1 1 Push the or key and move the cursor to the 1 Contrast 2 Push the Phase key 3 2 2 will be displayed Contrast 2 2 1 Push the or key and change the LCD contrast va...

Страница 16: ... for between the display unit connection Model EMU2 CB1 DP 10 Warranty If you have any questions or the product is broken down contact our sales representative near you The charge free warranty is effective until the earlier of 1 year after the date of your purchase or 18 months after manufacturing Repair shall be charged for the case failures occur due to your intent or fault even during the char...

Отзывы: