- 6 -

Screen

Operation

Note

7(2) Setup the demand time

EMU4-LG1-MB

7(2)-1

1

 

In 7(2)-1, push the 

    or   

    key, and move the cursor to

the “6 Demand”.

2

Push the

   

    / Phase    key and 

3

7(2)-2 will be displayed.

[Demand]

0sec

5min

6min

7min

8min

9min

10min

11min

12min

13min

14min

15min

20min

25min

30min

 

7(2)-2

1

Push the   

    or   

    key, and change the Io/Ior demand time value.

2

Push the

   

    / Phase    key, and confirm the setting value.

3

7(2)-1 will be displayed.

 

8 Setup the electric energy equivalent rate

All models except for EMU4-LG1-MB

8-1.

1

 

In 8-1,

 

push the     

    or   

    key, and move the cursor to the 

“7 CONV.Wh”

2

Push the

 

    / Phase    key.

3

 

8-2 will be displayed.

8-2.

1

Push the

▲ ▼

   

key,  and change  the 

CONV.Rate

” 

value and 

unit.

2

Push the

   

    / Phase    key

 

, and confirm the setting value.

3

Transition to the following screen by the setting wiring type.

     

2 circuit measurement

To 8-3

     

non-2 circuit measurement 

To 8-1

 

[CONV.Rate]

0.001

10000

1.000

[Unit]

Non

Wh

kWh

MWh

2

3

kL

sec

min

hour

piece

set

kg

 

8-3.

1

In a similar way as 8-2, change the 

CONV.Rate

value and unit

 

of the

second circuit.

2

Push the

   

    / Phase    key, and confirm the setting value.

3

 

8-1 will be displayed.

 

9 Setup the current cut-off rate (All models except for EMU4-LG1-MB, EMU4-PX4 and EMU4-AX4)

9-1.

1

In 9-1

push the   

    or

 

    key

 

, and move the cursor to the 

“8 A Cut-off”.

2

Push the

   

    / Phase    key.

3

 

9-2 will be displayed.

9-2.

1

 

Push the

or

key, and change the set value.

2

Push the

   

/ Phase    key

 

, and confirm the setting value.

3

Transition to the following screen by the setting wiring type.

     

2 circuit measurement 

To 9-3

     

non-2 circuit measurement 

To 9-1

[A Cut-off]

0.1

50.0%

0.5

A cut-off rate…represent as the ratio of cut-off current

to rated current.

 

Measured value is 0A if it is less than the 

cut-off current.

9-3.

1

 

In a similar way as 9-2, change the

A Cut-off

” 

value of the second circuit.

2

Push the

   

    / Phase    key, and confirm the setting value.

3

9-1 will be displayed.

10

 

Setup the Simple measurement 

All models except for EMU4-LG1-MB, EMU4-PX4 and EMU4-AX4

10-1.

1

 

In 10-1,

 

push the   

    or   

    key, and move the cursor to the

“9 SimpleMEA”.

2

Push the

   

    / Phase    key.

3

 

10-2 will be displayed.

10-2.

1

Push the

or

key, and select

 

SimpleMEA ([On]

[Off]).

2

Push the

   

    / Phase    key, and confirm the setting value.

3

Transition to the following screen by the setting SimpleMEA

[On]

[Off]

[On] setting

 To 10-3

[Off] setting

 To 10-1

[SimpleMEA]

Off

On

SimpleMEA…The value set in the electric power and

the power factor as the fixed value. 

By measuring the current only, and 

calculating the values of the measurement

elements.

10-3.

1

Push the

▲ ▼

   

key, and change the power factor value

In the

 

SimpleMEA.

2

Push the

   

    / Phase    key,and confirm the setting value.

3

Transition to the following screen by the setting wiring type.

     

2 circuit measurement 

 To 10-4

     

non-2 circuit measurement 

 To 10-1

[FP Set]

-0.001

1.000

0.000

10-4.

1

In a similar way as 10-3, change the power factor value of the second circuit.

2

Push the

   

/ Phase    key, and confirm the setting value.

3

10-1 will be displayed.

11

   

Setup the Ior

 

difference conversion

EMU4-LG1-MB only

11-1.

1

In 11-1, push the   

    or   

    key

 

, and move the cursor to the

10 DIF.CONV

.

2

Push the

   

    / Phase    key.

3

11-2 will be displayed.

[DIF.CONV]

Off

On

DIF.CONV…To  calculate  the  amount  of  change  from

the Ior difference converted value.

11-2.

1

Push  the   

or   

key, and  select the  Ior  difference  converted  value

 

[On]

[Off]

2

Push the

   

/ Phase    key, and confirm the setting value.

3

Transition to the following screen by the setting DIF.CONV

[On]

[Off]

.

[On] setting 

 To 11-3

[Off] setting 

 To 11-1

[Measure]

5

 

MEA.Mode

6

 

Demand

7

 

CONV.Wh

[CONV.Rate]

1

.000

[Unit]

Non

         

[1]

[CONV.Rate]

1

.000

[Unit]

Non

         

[2]

[Measure]

7

 

CONV.Wh

8

 

A Cut-off

9

 

SimpleMEA

[SimpleMEA]

Off

[FP Set]

 

1.000

[1]

[FP Set]

 

1.000

[2]

[Measure]

6

 

Demand

7

 

CONV.Wh

8

 

A Cut-off

[DIF.CONV ]

 

Off

[Measure]

8

 

A Cut-off

9

 

SimpleMEA

10

DIF.CONV

[A Cut-off]

0

0.5

[1]

[A Cut-off]

[2]

[Measure]

4

 

DISP.Mode

5

 

MEA.Mode

6

 

Demand

[Demand]

Io/Ior

5min

0

0.5

Содержание EMU4-D65

Страница 1: ...ollowing setup is need before using EMU4 D65 The one always in one system is the Master set Other display unit of please to Slave configuration The wrong setting and it does not work 3 3 Installation and connection Before installing and connecting the unit read the instruction manual without fail For safety the unit shall be installed and connected by experts in electrical work When threading and ...

Страница 2: ...uit LED A circuit number on display lights up Moreover LED of the circuit number blinks at the time of alarm occuring OUT 1 Connector Use for connection with a next display unit OUT 2 Connector Use for connection with a next display unit IEC rail attachment Use when installating on IEC rail Master LED The light is switched on at the time of operation key Change of display item and selection of a m...

Страница 3: ...antaneous power failure alarm Setup for the condition of monitoring breaker alarm Monitoring for measurement data Please refer to the instruction manual Detailed edition Please refer to the instruction manual Detailed edition Reset the Max Min data and alarm data Preset the value of Wh and varh Setup Setup Reset Set Connection test Pulse output test Alarm output test Communication test Test mode i...

Страница 4: ...key and change the set value 2 Push the Phase key and confirm the setting value 3 3 6 will be displayed 3 6 1 Push the key and change the set value 2 Push the Phase key and confirm the setting value 3 3 1 will be displayed 4 Setup the primary current All models except for EMU4 LG1 MB EMU4 PX4 and EMU4 AX4 4 1 1 In 4 1 Push the and move the cursor to the 3 A rate 2 Push the Phase key 3 4 2 will be ...

Страница 5: ...ate UNB V Voltage unbalance rate HA Harmonics current HV Harmonics voltage 5 4 1 Push the or key and change the HA HV value 2 Push the Phase key 3 5 1 will be displayed HA HV r m s In case of the model EMU4 BM1 MB HA HV can not be set r m s to display the RMS value of harmonic current or harmonic voltage The not be displayed to display the distortion rate and content rate of harmonic current or ha...

Страница 6: ...ase key and confirm the setting value 3 9 1 will be displayed 10 Setup the Simple measurement All models except for EMU4 LG1 MB EMU4 PX4 and EMU4 AX4 10 1 1 In 10 1 push the or key and move the cursor to the 9 SimpleMEA 2 Push the Phase key 3 10 2 will be displayed 10 2 1 Push the or key and select SimpleMEA On Off 2 Push the Phase key and confirm the setting value 3 Transition to the following sc...

Страница 7: ...ush the key and change the number of moving average 2 Push the Phase key and confirm the setting value 3 12 9 will be displayed 12 9 1 Push the key and change the upper limit lower limit and unit 2 Push the Phase key and confirm the setting value 3 12 10 will be displayed 12 10 1 Push the or key and select the AD converted On Off 2 Push the Phase key and confirm the setting value 3 Transition to t...

Страница 8: ...ill be displayed 13 2 4 1 Push the or key and select the multiplying factor displayed 2 Push the Phase key 3 13 2 5 will be displayed 13 2 5 1 Push the or key and select the multiplying factor displayed 2 Push the Phase key 3 13 2 1 will be displayed 14 Save the settings 14 1 14 2 1 After setting all of the items and push the Setup key 2 14 1 will be displayed 3 When save the settings push the or ...

Страница 9: ...setting To 2 6 Contact setting To 2 7 2 6 1 Push the key and change the CONV Rate value and unit 2 Push the Phase key and confirm the setting value 3 2 8 will be displayed 2 7 1 Push the or key and select thereset mode 2 Push the Phase key 3 2 8 will be displayed 2 8 1 Push the or key and select the input method Non Contact Pulse 2 Push the Phase key 3 Transition to the following screen by the set...

Страница 10: ...tput EMU4 HM1 MB EMU4 A2 EMU4 VA2 EMU4 PX4 EMU4 AX4 I O 1 Input 2 OP Time 3 Output OP Time Off 1 OP Time Mode A 1 OP Time Off 2 OP Time Mode A 2 Model EMU4 PX4 or 2 circuits measuring only 2 circuits measuring only OP Time Off 3 OP Time Off 4 4 1 1 In 4 1 Push the or key and move the cursor to the 3 Output 2 Push the Phase key 3 4 2 will be displayed EMU4 HM1 MB EMU4 A2 EMU4 VA2 Output Non Pulse A...

Страница 11: ...1 MB EMU4 LG1 MB 3 1 1 In 3 1 Push the or key and move the cursor to the 2 Baut rate 2 Push the Phase key 3 3 2 will be displayed Baut rate 2400 4800 9600 19200 38400 3 2 1 Push the or key and select the baut rate 2 Push the Phase key 3 3 1 will be displayed 4 Setup the parity EMU4 BM1 MB EMU4 HM1 MB EMU4 LG1 MB 4 1 1 In 4 1 Push the or key and move the cursor to the 3 Parity 2 Push the Phase key ...

Страница 12: ...ng all of the items push the or key and move the cursor to the OK 7 Push the Phase key and clock setting changed Note 2 8 2 2 will be displayed 9 When to exit the clock setup push the or key and move the cursor to the OK and push the Phase key If select the Cancel return to 1 1 10 After completing the settings saving and 1 1 will be displayed Year 00 01 02 13 99 Month 01 02 03 04 12 Day 01 02 29 3...

Страница 13: ...ring 2 Push the Phase key 3 2 2 will be displayed Wiring 1P2W 1P3W 3P3W 3P4W 3P4W setting is EMU2 RD 4W only 3P4W fixed 2 4 C In the case of the model MDU2 displays all 1P2W 3P4W but can not be set for 3P4W in the case of connection breaker 3 pole products 2 2 1 Push the or key and change the set value 2 Push the Phase key and confirm the setting value 3 2 1 will be displayed 3 Setup the primary v...

Страница 14: ...2kW Wfull 120kW 0 01 0 1 1 10 120kW Wfull 1200kW 0 1 1 10 100 1200kW Wfull 12000kW 1 10 100 1000 12000kW Wfull 120000kW 10 100 1000 10000 120000kW Wfull 100 1000 10000 100000 7 2 1 Push the or key and change the set value 2 Push the Phase key and confirm the setting value 3 7 1 will be displayed 8 Setup 1 3Change MDU2 8 1 1 In 8 1 Push the or key and move the cursor to the 7 1 3Change 2 Push the P...

Страница 15: ...ote 1 Transition to the setup mode 1 1 1 Push the Setup key in operation mode 2 1 1 will be displayed 1 In 1 1 Push the or key and move the cursor to the 3 Display 2 Push the Phase key 3 2 1 will be displayed 2 Setup the LCD contrast 2 1 1 Push the or key and move the cursor to the 1 Contrast 2 Push the Phase key 3 2 2 will be displayed Contrast 2 2 1 Push the or key and change the LCD contrast va...

Страница 16: ... for between the display unit connection Model EMU2 CB1 DP 10 Warranty If you have any questions or the product is broken down contact our sales representative near you The charge free warranty is effective until the earlier of 1 year after the date of your purchase or 18 months after manufacturing Repair shall be charged for the case failures occur due to your intent or fault even during the char...