Part Name
Check Points
Thermistors
Disconnect the connector then measure the resistance with a tester.
(At ambient temperatures of 10 - 30°C.)
Flow sensor
Thermistor
Normal
Abnormal
TH1
4.3 - 9.5 kΩ
Open or short
TH2
THW1
THW2
THW5
THW6
THW7
THW8
THW9
THWB1
40 - 100 kΩ
Open or short
THWB2
Yellow
White
Green
Brown
Flow signal V
5V DC
CN1A
1
4
Flow signal
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
0
20
40
60
80
100
Flow [l/min]
Flow output signal
[V]
0.35V
55
OCH571
Содержание ecodan EHPX-VM2C
Страница 83: ...83 OCH571 ...