64
O-ring
DISASSEMBLY PROCEDURE
PHOTOS
Photo 7-1
7. How to remove the booster heater
(1) Remove the front panel. (Refer to Procedure 1.)
(2)
Disconnect the booster heater lead wires from the CNBHT
connector on the controller board and from the BHC1
(Lead wire No.1, No.2 and No.3) and BHC2 (Lead wire
No.4, No. 5 and No.6) contactors respectively. (Photo 7-1)
(3)
Swing the control box to the front. (Refer to Procedure 4.)
Note: Do not mix up the lead wire numbers when
re-connecting the lead wires to the contactors as
the lead wire numbers are different dependent on
the models.
<E*S* series>
(4) Remove the pump valve. (Refer to Procedure 5.)
(5) Remove the flow sensor. (Refer to Procedure 6.)
(6) Remove the L joint and the pipe (L-F.S.) by detaching the
quick connection. (Photo 7-2)
•
When reinstalling the quick connection, use new O-ring.
•
Refer to page 77 for how to attach and detach the quick
connection.
(7) Remove the flare nut (Photo 7-2).
(8) Remove the pipe (P.V.-B.H.) by detaching the quick
connection. (Photo 7-2)
•
When reinstalling the quick connection, use new O-ring.
•
Refer to page 77 for how to attach and detach the quick
connection.
(9) Remove the two screws that hold the heater stay onto
the back panel. Lift the booster heater slightly and
remove the booster heater with the heater stay from the
back panel. (Photo 7-2 and 7-3)
(10) Remove the 2 screws on the back of the heater stay
and remove the heater stay from the booster heater.
(Photo 7-3)
•
Reuse the removed heater stay and the heater stay
fixing screws.
Model
Lead wire No.
Contactor
EHSC-VM6C
EHSC-VM6EC
No.1
BHC1-U
No.2
BHC1-V
No.3
BHC2-U
No.4
BHC2-V
EHSC-YM9C
EHSC-YM9EC
EHSC-TM9C
EHPX-YM9C
No.1
BHC1-U
No.2
BHC1-V
No.3
BHC1-W
No.4
BHC2-U
No.5
BHC2-V
No.6
BHC2-W
EHSD-VM2C
EHSC-VM2C
EHSC-VM2EC
ERSD-VM2C
EHPX-VM2C
ERSC-VM2C
No.1
BHC1-U
No.2
BHC1-V
Refer to 6. WIRING DIAGRAM
Photo 7-2
(
E*S* series)
Photo 7-3
BHC2
BHC1
Booster heater
connector (CNBHT)
Flare nut
Control box
Heater stay
Screw
O--ring
*
The photos shown are of the EHSC-YM9C model.
Back panel
Cable strap
Cable strap Coated clamp
Earth leakage
breakers (ECB1)
Screw
Nut
Flow
sensor
Heater stay
Screws
Booster
heater
Pump valve
No.1 No.2 No.3
No.4 No.5 No.6
L joint
Pipe
(L-F.S.)
Nut
Pipe
(P.V.-B.H.)
Quick
connection
Quick
connection
OCH571